Plan Review Notes
Plan Review Notes For Permit 16010112
Permit Number 16010112
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-14 10:58:27THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE RISER AS SHOWN ON THE DRAWINGS DOES NOT MATCH
 THE DEVICE COUNT ON PLANS.
 2. NEWLY INSTALLED FIRE ALARM SYSTEMS SHALL BE
 MONITORED AS INDICATED BY THE SEQUENCE OF OPERATION,
 BUT THE SIGNAGE SHOWN ON THE PLANS CONFLICT WITH THIS
 REQUIREMENT. WALL PLACARDS HAVE BEEN CROSSED OUT ON THE
 PLANS. REVISE THE DRAWING ACCORDINGLY.
 3. PER NFPA REQUIREMENTS YOU SHALL PROVIDE 75 DB AT THE
 PILLOW AT EACH SLEEPING AREA. REVISE YOUR DRAWING AND
 DEVICE PLACEMENT FOR COMPLIANCE WITH SUCH.
 4. ONCE DEVICE COUNT GETS ADJUSTED TO MEET MINIMUM
 AUDIBILITY REQUIREMENTS, ADJUST THE RISER DIAGRAM,
 BATTERY AND VOLTAGE DROP CALCS AS REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,