| Date |
Text |
| 2016-01-30 06:38:52 | 1) SUBMIT TWO COPIES OF THE TANK DETAIL SHOWING THE |
| | INTERIOR (SECTION DETAIL) OF THE TANK. THE TANK SHALL |
| | COMPLY WITH F.A.C. RULE 64-6.013 (7). SEE BELOW: |
| | (7) GREASE INTERCEPTORS ARE NOT REQUIRED FOR A |
| | RESIDENCE. HOWEVER, ONE OR MORE GREASE INTERCEPTORS ARE |
| | REQUIRED WHERE GREASE WASTE IS PRODUCED IN QUANTITIES |
| | THAT COULD OTHERWISE CAUSE LINE STOPPAGE OR HINDER |
| | SEWAGE DISPOSAL. THE DESIGN OF GREASE INTERCEPTORS |
| | SHALL BE BASED ON STANDARDS FOUND IN PARAGRAPH (A) |
| | BELOW. IN ADDITION, THE FOLLOWING GENERAL REQUIREMENTS |
| | FOUND IN PARAGRAPHS (B), (C), AND (D), APPLY WHEN |
| | DETERMINING THE PROPER USE AND INSTALLATION OF A GREASE |
| | INTERCEPTOR USED AS A COMPONENT OF AN ONSITE SEWAGE |
| | TREATMENT AND DISPOSAL SYSTEM. |
| | (A) THE INLET INVERT SHALL DISCHARGE A MINIMUM 2 1/2 |
| | INCHES ABOVE THE LIQUID LEVEL LINE AND THE OUTLET PIPE |
| | SHALL HAVE A TEE WITH A MINIMUM DIAMETER OF 4 INCHES |
| | THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF THE |
| | TANK. |
| | (D) SIZING OF GREASE INTERCEPTORS SHALL BE BASED ON THE |
| | EQUATIONS BELOW. THE MINIMUM VOLUME OF ANY GREASE |
| | INTERCEPTOR SHALL BE 750 GALLONS AND THE MAXIMUM VOLUME |
| | OF AN INDIVIDUAL SINGLE GREASE INTERCEPTOR CHAMBER |
| | SHALL BE 1250 GALLONS. WHEN THE REQUIRED EFFECTIVE |
| | CAPACITY OF THE GREASE INTERCEPTOR IS GREATER THAN 1250 |
| | GALLONS, INSTALLATION OF MULTI-CHAMBERED GREASE |
| | INTERCEPTORS OR GREASE INTERCEPTORS IN SERIES IS |
| | REQUIRED. |
| | 2)SUBMIT A DETAIL OF THE REQUIRED SAMPLING POINT. AS |
| | DESCRIBED IN THE NOTES ON THE PLANS, THE SAMPLING POINT |
| | DOES NOT MEET THE INTENT OF THE CITY'S REQUIREMENT.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 3)THE PLANS CALL FOR 1250 GALLON TANKS BUT A DETAIL HAS |
| | BEEN SUBMITTED FOR 1350 GALLON TANKS. TANKS EXCEEDING |
| | 1250 SHALL BE MULT-CHAMBERED. SUBMIT DETAILS FROM THE |
| | MANUFACTURER SHOWING THE INTERIOR OF THE TANK AND THE |
| | CHAMBERS AND COMPLIANCE WITH F.A.C. 64E-6.013 (7) (A) & |
| | (D). |
| | 4) FIBERGLASS & POLYETHYLENE TANKS SHALL COMPLY WITH |
| | F.A.C. RULE 64E-6.013 (6) (B)(C).A TEST REPORT FROM AN |
| | INDEPENDENT TESTING LABORATORY IS REQUIRED TO |
| | SUBSTANTIATE THAT INDIVIDUAL RECEPTACLE DESIGNS AND |
| | MATERIAL FORMULATIONS MEET THESE REQUIREMENTS. THIS |
| | INFORMATION/REPORT SHOULD BE OBTAINABLE FROM THE |
| | MANUFACTURER. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |