2016-04-06 13:39:30312 23RD STREET
 PERMIT #16010052
 MASTER #14120431
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET FP-3: THE HYDRAULIC CALCULATIONS
 FOR "PARKING A1" INCORRECTLY INCLUDE HYDRAULIC NODES
 M3, M4 AND M5 WHICH ARE A PART OF THE RETAIL A2
 HYDRAULIC CALCULATIONS.
  
 REPEAT COMMENT - SHEET FP-3: THE HYDRAULIC CALCULATIONS
 FOR "PARKING A1" SUPPORT 4 SPRINKLERS BEING SUPPLIED
 FROM AN 1.25-INCH BRANCHLINE; HOWEVER, SEVERAL
 BRANCHLINES SUPPLY 5 AND 6 SPRINKLERS FROM 1.25-INCH
 PIPING WHICH IS NOT SUPPORTED BY HYDRAULIC
 CALCULATIONS.
  
 REPEAT COMMENT - SHEET FP-3: THE HYDRAULIC CALCULATIONS
 ARE MISSING 3 FLOW POINTS FROM NODES #206, #207 & #209.
 THESE FLOWS WILL ADD ANOTHER 80 GPM TO THE TOTAL FLOW
 REQUIRED. ADDITIONALLY, THE PLANS SHOW 1.25-INCH
 BRANCHLINE PIPING SUPPLYING ALL SPRINKLERS ON THE PLAN;
 HOWEVER, THE HYDRAULIC CALCULATIONS INDICATE THAT THE
 BRANCHLINE PIPING NEEDS TO BE LARGER. FOR INSTANCE NODE
 B201 TO NODE B203 INDICATES THAT 2-INCH PIPING IS
 NEEDED; HOWEVER, THE PLAN SHOWS 1.25-INCH. THIS IS ALSO
 TRUE FOR NODES B203 TO H204 AND FOR NODES H204 TO M7.
 CORRECT ALL PIPE SIZES AND ENSURE THEY ARE CONSISTENT
 THROUGHOUT THE PLAN.
  
 REPEAT COMMENT - SHEET FP-5: THE PIPE SIZING IS NOT
 CONSISTENT THROUGHOUT THIS PLAN, FOR INSTANCE:
  
 THE PIPING LOCATED IN THE NORTH PORTION OF UNIT B1 HAS
 THE FOLLOWING PIPING SCHEDULE:
 1 - 2 SPRINKLERS = 1.0-INCH BRANCHLINE
 3 - 5 SPRINKLERS = 1.25-INCH BRANCHLINE
 6 - 9 SPRINKLERS = 1.5-INCH BRANCHLINE
  
 THE PIPING LOCATED IN THE SOUTH PORTION OF UNIT B1 HAS
 A DIFFERENT PIPING SCHEDULE:
 1 - 4 SPRINKLERS = 1.0-INCH BRANCHLINE
  
 UNIT A2 ALSO HAS TWO DIFFERENT PIPING SCHEDULES:
 1 -4 SPRINKLERS = 1.0-INCH BRANCHLINE
  
 AND
  
 1 - 2 SPRINKLERS = 1.0-INCH BRANCHLINE
 3 - 7 SPRINKLERS = 1.5-INCH BRANCHLINE
  
 SHEET FP-5: SOME OF THE UNIT B2S SHOW AS MANY AS 10 AND
 11 SPRINKLERS SUPPLIED BY 1.5-INCH PIPING WHICH IS NOT
 SUPPORTED BY THE HYDRAULIC CALCULATIONS.
  
 NOTE: A SEPARATE UNDERGROUND FIRELINE (UG FIRELINE)
 PERMIT IS NEEDED FOR THE INSTALLING CONTRACTOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE