2016-02-02 14:45:14312 23RD STREET
 PERMIT #16010052
 MASTER #14120431
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS DO NOT REFERENCE CONFORMANCE WITH NFPA 14.
  
 THE PLANS ONLY INDICATE CONFORMANCE WITH NFPA 13;
 HOWEVER, THE HYDRAULIC CALCULATIONS AND DESIGN INDICATE
 A DESIGN DENSITY OF 0.05 FOR 4 SPRINKLERS WHICH IS
 ASSOCIATED WITH NFPA 13R.
  
 IN ORDER TO USE QUICK-RESPONSE SPRINKLERS IN LIEU OF
 RESIDENTIAL SPRINKLERS WITHIN THE DWELLING UNIT, THE
 WHOLE DWELLING UNIT NEEDS TO BE PROTECTED WITH FOUR OR
 FEWER SPRINKLERS, SO THE ROOM DESIGN METHOD MIGHT BE
 MORE EFFICIENT. PER NFPA 13R SECTION 6.2.1.3, LISTED
 QUICK-RESPONSE SPRINKLERS SHALL BE PERMITTED TO BE
 INSTALLED IN DWELLING UNITS MEETING THE DEFINITION OF A
 COMPARTMENT, AS DEFINED IN SECTION 3.3, WHERE NO MORE
 THAN FOUR SPRINKLERS ARE LOCATED IN THE DWELLING UNIT.
 NFPA 13R REQUIRES THE ENTIRE DWELLING UNIT TO BE SMALL
 ENOUGH TO BE PROTECTED WITH FOUR SPRINKLERS IN ORDER TO
 APPLY 6.2.1.3. THIS REQUIREMENT DOES NOT MEAN THAT EACH
 COMPARTMENT NEEDS ONLY FOUR SPRINKLERS, IIT MEANS THAT
 THE WHOLE DWELLING UNIT, INCLUDING ALL OF THE SLEEPING
 ROOMS, CLOSETS, BATHROOMS, FOYERS, AND NOOKS, HAS TO BE
 SMALL ENOUGH TO BE PROTECTED WITH FOUR OR FEWER
 SPRINKLERS. IF QUICK-RESPONSE SPRINKLERS ARE USED IN
 ACCORDANCE WITH 6.2.1.3, THE SYSTEM MUST BE ABLE TO
 PROVIDE A MINIMUM DENSITY OF 0.1 GPM/FT2 (4.1 MM/MIN)
 OVER THE DESIGN AREA, WHICH IS THE ENTIRE DWELLING UNIT
 IN THIS CASE (USING THE ?ROOM DESIGN METHOD? FROM NFPA
 13, 11.2.3.3). QUICK-RESPONSE SPRINKLERS ARE CURRENTLY
 NOT EVALUATED FOR PERFORMANCE AT LOWER DENSITIES SUCH
 AS 0.05 GPM/FT2 (2.04 MM/MIN). THE MINIMUM DENSITY
 REQUIREMENT HAS ALSO BEEN ADDED TO 6.2.1.4, SINCE
 QUICK-RESPONSE SPRINKLERS ARE PERMITTED BY THAT
 PARAGRAPH AS WELL. THE MINIMUM DENSITY OF 0.10 GPM/FT2
 (4.1 MM/MIN) IS CONSISTENT WITH THE REQUIREMENTS FOR
 THE USE OF QUICK-RESPONSE SPRINKLERS IN NFPA 13.
  
 NOTE: CHANGING THE QUICK RESPONSE SIDEWALL SPRINKLERS
 TO RESIDENTIAL SIDEWALL SPRINKLERS WILL RESULT IN THE
 MAJORITY OF THE SIDEWALL SPRINKLERS BEING OBSTRUCTED BY
 THE ADJACENT SOFFITS DUE TO THE SPRINKLER LOCATION
 DIFFERENCES AND OBSTRUCTION RULE DIFFERENCES.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 NOTE: A SEPARATE UNDERGROUND FIRELINE (UG FIRELINE)
 PERMIT IS NEEDED FOR THE INSTALLING CONTRACTOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  