| 2016-01-28 18:35:48 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. REVISION |
| | FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS ACCEPTABLE. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CROSS |
| | VENTILATION CREDIT. PROVIDE COMPLETE INFORMATION |
| | SHOWING HOW THE PLANS COMPLY WITH ALL THE REQUIREMENTS |
| | OF SEC. R405.7.4 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) ITEM #5 OF ENERGY CALCULATIONS STATE THAT THE |
| | CALCULATIONS ARE NO WORST CASE SCENARIO, BUT PAGE 2 OF |
| | 4 STATES THAT HOUSE WAS ROTATED 90 DEGREES. THIS IS NOT |
| | CLEAR. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: ENERGY CALCULATIONS MAY BE DONE FOR WORST CASE |
| | SCENARIO, BUT EQUIPMENT SIZING CALCULATIONS NEED TO BE |
| | DONE TO THE ACTUAL ORIENTATION OF THE BUILDING. |
| | |
| | B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS |
| | REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | C) REVISE THE CLIMATE ZONE SHOWN ON PAGE 2 OF 4. SEE |
| | TABLE C301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | D) REVISE THE TYPE OF ROOF SHOWN ON PAGE 2 OF 4. PLANS |
| | SUBMITTED DON'T SHOW HIP ROOF. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | E) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. SEC. R103.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | F) COMPLETE THE CHECK LIST ON TABLE 402.4.1.1 |
| | SUBMITTED. |
| | |
| | G) COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY |
| | CARD SUBMITTED. |
| | |
| | NOTE: |
| | LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING |
| | THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 3- WINDOW AND DOOR SCHEDULE ON SHEET A-3.0: ENTRY DOOR |
| | SAYS "NR". CLARIFY WHY THE ENTRY DOOR DOESN'T HAVE TO |
| | COMPLY WITH THE EGRESS REQUIREMENTS. SEC. R11 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED TO $150,000. THE PERMIT FEE |
| | BALANCE IS $973.38. SEC. 109.3 CITY AMENDMENTS. |
| | |
| | 5- REVISE THE DESIGN PARAMETERS NOTE ON SHEET A-3.0: |
| | THE BUILDING DOESN'T HAVE A HIP ROOF. THE DESIGN |
| | PRESSURES ON A HIP ROOF AND A GABLE ROOF ARE DIFFERENT. |
| | REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 6- SIZE OF FOOTING S1 SHOWN ON SHEET S-1.0 DOESN'T |
| | MATCH SIZE SHOWN ON TYPICAL WALL SECTION. |
| | REVISE/CLARIFY AS REQUIRED. WHICH ONE IS THE CORRECT |
| | SIZE?. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 7- RE-SUBMIT PRODUCT APPROVAL REQUIRED BY FAC |
| | 61G20-3.002(33) FOR: EXTERIOR DOORS. FLORIDA PRODUCT |
| | APPROVAL FL11136-R1 SUBMITTED IS FOR THE 2010 CODE |
| | VERSION. NEED THE CURRENT 2014 CODE VERSION. |
| | NOTE: REVISE ALL PRODUCT APPROVAL NUMBERS ON SHEET |
| | A-3.0 AS WELL. |
| | |
| | 8- DESIGNER OF RECORD TO APPROVED ABOVE PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL. SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 9- REVISE SURVEY. BUILDING IS LOCATED IN FLOOD ZONE "B" |
| | NOT "C". SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSIGN EACH |