| 2016-09-17 10:01:32 | 1) SHT.A0.02 - NOTES: THE NOTES REFER TO ONLY THE FIRST |
| | FLOOR UNITS COMPLYING WITH THE FAIR HOUSING ACT. SINCE |
| | THERE IS AN ELEVATOR IN THIS BUILDING AND THERE ARE A |
| | MINIMUM OF 4 DWELLING UNITS IN THE BUILDING, ALL THE |
| | UNITS SHALL COMPLY WITH THE REQUIREMENTS FOR FAIR |
| | HOUSING. PLEASE REVISE THE NOTE. |
| | 2) THE SQUARE FOOTAGE CALCULATIONS FOR THE ROOF DRAINS |
| | SHALL ALSO INCLUDE ANY AREAS OF SLOPED ROOFS THAT DRAIN |
| | ONTO THE LOWER ROOF. I DO NOT SEE THIS ADDED INTO THE |
| | ROOF DRAIN CALCULATIONS. CLARIFY. 2014 FPC SEC.1106.2. |
| | SHT. A2.02. |
| | 3) SHT. A8.03 - THE REINFORCEMENT FOR THE GRAB BAR FOR |
| | THE SHOWER SHALL BE 32 INCHES MAXIMUM TO THE BOTTOM OF |
| | THE REINFORCEMENT AND 38 INCHES MINIMUM TO THE TOP OF |
| | THE REINFORCEMENT PER REQUIREMENT 6 OF THE GUIDELINES. |
| | SHOW THIS ON THE PLAN. |
| | 4) REVISE THE RISER IDENTIFICATION TAGS FOR THE WATER, |
| | CONDENSATE, PAN DRAINS. THEY ARE BASICALLY ALL LABELD |
| | R1 OR R1A. THIS IS EXTREMELY CONFUSING IN THE REVIEW |
| | STAGE AND WILL ALSO BE CONFUSING DURING THE INSPECTION |
| | PROCESS. WHY NOT IDENTIFY THE RISERS AS TO THEIR USE? |
| | C=CONDENSATE, DP=DRIP PANS, W1, W2, W3, ETC. |
| | 5) SHT. P3.01 - RISER S/1A IS SHOWN ON THE SANITARY |
| | RISER ON P5.04 BUT IS NOT SHOWN ON P3.01.IT APPEARS AS |
| | THOUGH IT IS MISLABELED AS RISER S/1B ON SHT. P3.01. |
| | CLARIFY. |
| | 6) SHT. A4.02 - THE CLEAR FLOOR SPACE ADJACENT TO THE |
| | SHOWER OPENING SHALL BE FLUSH WITH THE CONTROL WALL. IT |
| | WAS CORRECTED ON SHT. A4.03 BUT NOT ON A4.02. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |