2016-09-13 11:36:223RD REVIEW FBC-2014 MECHANICAL
 PERMIT #15120897
 9/13/16
  
 1) AC CALCULATIONS A, D, & M FOR THE SE CORNER UNITS
 INDICATE 1.0 TONS OF COOLING (12,000 BTU'S) . UNITS
 SELECTED, AS SHOWN IN THE ENERGY CALCULATIONS, ARE
 21,200 & 26,300 BTU'S. THERE IS NO EXCEPTION UNDER
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION THAT ALLOWS
 THIS INCREASED SIZE IN TONNAGE, HOWEVER AN INCREASE TO
 THE 16,700 BTU (1-1/2 TON) SYSTEM IS ACCEPTABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER