| 2016-07-28 17:20:50 | PERMIT # 15120897 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 3RD REVIEW |
| | FAILED REVIEW COMMENTS: |
| | |
| | 1) REPEAT COMMENT (3RD TIME BEING NOTED): ENGINEERED |
| | FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS |
| | ARE REQUIRED FOR A GENERAL BUILDING PERMIT. THESE |
| | DOCUMENTS ARE NOT INCLUDED IN THE RESUBMISSION. PER |
| | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 2) 7/28/16: A LETTER WAS SUBMITTED BY THE CONTRACTOR |
| | AND SEALED BY THE ENGINEER OF RECORD. THE LETTER |
| | SUBMITTED FAILED TO ADDRESS ALL OF THE LISTED |
| | REQUIREMENTS FOR THE ENGINEERED FIRE PROTECTION |
| | SYSTEMS, AS LISTED UNDER FAC 61G15-32. AN EMAIL WAS |
| | SENT OUTLINING THESE REQUIREMENTS TO ALL PARTIES. |
| | ADDITIONALLY, ALL PARTIES HAVE BEEN ADVISED THAT A FEE |
| | MAY BE ASSESSED FOR CONTINUED SUBMISSIONS THAT FAIL TO |
| | BE IN COMPLIANCE. |
| | |
| | |