| 2016-09-14 10:09:24 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120897 |
| | ADD: 7120 OKEECHOBEE BLVD. BLDG. TYPE III/ BLDG. # 5. |
| | CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 4TH REVIEW |
| | DATE: WED. SEPT. 14/2016 |
| | NOTE: THIS REVIEW IS FOR BUILDING TYPE III, NOT FOR THE |
| | SITE PLAN, OR ANY ASSOCIATED AMENITIES. |
| | SITE SOILS REPORT : SEE PERMIT: 16020377 RECREATION/ |
| | LEASE CENTER |
| | |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) BUILDING PROVISO: PRODUCT APPROVALS TO BE DEFERRED |
| | SUBMITTALS. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. COMPONENTS & |
| | CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 2A) DEFERRED SUBMITTALS. NOTE THIS NOTE APPLIES TO |
| | FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) DEFERRED SUBMITTAL. THIS NOTE APPLIES TO WALLS ON |
| | ALL FLOORS. WALL TYPES FOUND ON SHEET A8.01, THE WALL |
| | TYPES DO NOT PROVIDE THE REQUIRED STC RATING NOR TEST |
| | RESULTS IN ACCORDANCE WITH: FBC-B 2014 1207.2 AIR-BORNE |
| | SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) DEFERRED SUBMITTAL. NOTE THIS IS A VERY RESTRICTIVE |
| | REQUIREMENT!!! TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 |
| | 720.2 CONCEALED INSTALLATION. INSULATING MATERIALS, |
| | WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE |
| | OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | 3) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & E5.01 |
| | CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5 |
| | AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR |
| | OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE |
| | WITH UL 325. IF THERE IS A POWER FAILURE OR A |
| | MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS |
| | HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) PROVISO: SHEET A8.02 DETAIL # 11 SHOWS A SLIDING |
| | GLASS DOOR. THE HEIGHT OF THE SLIDING GLASS DOOR SILL |
| | WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT |
| | APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 . |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |