Plan Review Notes
Plan Review Notes For Permit 15120897
Permit Number 15120897
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2016-04-19 15:57:53SIGNATURE S PLAN REVIEW
 W. P. B. PERMIT: 15120897
 ADD: 7120 OKEECHOBEE BLVD. BLDG.#5/ TYPE III
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 10/2016
 ACTION: DENIED
  
 1A) THE ENERGY GAUGE SUMMIT ASHRAE FORM 1-18 PAGES,
 SIGNED AND SEALED BY CHARLES KILLINGSWORTH P. E. 015094
 IS NOT A DIGITAL SIGNATURE. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEES SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 1B) HEAT LOAD CALCULATIONS, SIGNED AND SEALED BY
 CHARLES KILLINGSWORTH P. E. 015094 IS NOT A DIGITAL
 SIGNATURE. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEES SIGNATURE SHALL NOT BE
 USED ON ELECTRONICALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS HAVE ELECTRONIC SIGNATURES. THE CITY NO LONGER
 ACCEPTS THE PEDDS SIGNATURE, 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR
 IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND
 SHALL ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT;
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEES SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) THE MEP SHEETS FROM THE 1ST REVIEW THAT WERE NOT
 CHANGED, THERE IS NO SIGNATURE THE RESUBMITTED SHEETS
 UNDER THE 2ND REVIEW ARE DIGITALLY SIGNED BY RANDALL
 STOFFER DO NOT HAVE THE SIGNATURE LINKED TO BE ABLE FOR
 VERIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  