| 2016-02-18 06:13:24 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | SITE LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR IF |
| | PART OF DESIGN, FIRE/DOMESTIC PUMPS, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| | ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS, |
| | ETC. A NOTE WILL SUFFICE. |
| | 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE |
| | REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM |
| | COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A |
| | WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN |
| | FOR THIS PROJECT. A NOTE WILL SUFFICE. |
| | 3. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- |
| | COMPLETION DOCUMENTS PER CODE SECTION. |
| | 4. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION |
| | PROVIDED BY UTILITY FOR APPROVAL. NEC 110.24 FBC 107 |
| | 5. ADD A NOTE REGARDING THE REQUIREMENTS OF FBC RES 314 |
| | SMOKE/CO DETECTORS, SEE VERBIAGE IN THE CODE AS TO |
| | PLACEMENTS AND REQUIREMENTS. |
| | 6. PLEASE CLARIFY THE SELECTION OF A #1 CONDUCTOR FOR |
| | THE ELEVATOR MOTOR 175A/3P OVERCURRENT SELECTION. SEE |
| | NEC 310.15B16 AND 430.22 |
| | 7. PLEASE ADD A FIRE STOP DETAIL FOR THE FEEDER |
| | PENETRATIONS THROUGH THE BUILDING FLOORS. FBC 107.3 |
| | 8. PER NEC 230.2 SPECIAL PERMISSION REQUIRED BY AHJ FOR |
| | THE TWO SERVICE LATERALS SHOWN TO THE BUILDING, TO BE |
| | SUBMITTED IN WRITING. |
| | 9. LABEL MAINS IN THE ELECTRICAL ROOM TO INDICATE MAIN |
| | 1 OF 2 AND 2 OF 2, ALSO COMPLY WITH THE REQUIRED |
| | SIGNAGE TO ASSIST FIRST RESPONDERS. NEC 230.70B |
| | 10. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |