2016-07-28 17:19:32PERMIT # 15120896
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 5TH REVIEW
 FAILED REVIEW COMMENTS:
  
 1) REPEAT COMMENT (5TH TIME BEING NOTED): ENGINEERED
 FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS
 ARE REQUIRED FOR A GENERAL BUILDING PERMIT. THESE
 DOCUMENTS ARE NOT INCLUDED IN THE RESUBMISSION. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 2) 7/28/16: A LETTER WAS SUBMITTED BY THE CONTRACTOR
 AND SEALED BY THE ENGINEER OF RECORD. THE LETTER
 SUBMITTED FAILED TO ADDRESS ALL OF THE LISTED
 REQUIREMENTS FOR THE ENGINEERED FIRE PROTECTION
 SYSTEMS, AS LISTED UNDER FAC 61G15-32. AN EMAIL WAS
 SENT OUTLINING THESE REQUIREMENTS TO ALL PARTIES.
 ADDITIONALLY, ALL PARTIES HAVE BEEN ADVISED THAT A FEE
 MAY BE ASSESSED FOR CONTINUED SUBMISSIONS THAT FAIL TO
 BE IN COMPLIANCE.
  
  