Plan Review Notes
Plan Review Notes For Permit 15120896
Permit Number 15120896
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2016-07-18 10:50:33PERMIT # 15120896
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 4TH REVIEW
 FAILED REVIEW COMMENTS:
  
 1) REPEAT COMMENT (3RD TIME BEING NOTED): ENGINEERED
 FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS
 ARE REQUIRED FOR A GENERAL BUILDING PERMIT. THESE
 DOCUMENTS ARE NOT INCLUDED IN THE RESUBMISSION. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
  