| Plan Review Notes For Permit 15120896 |
| Permit Number |
15120896 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-07-01 11:54:36 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120896 | | | 7/1/2016 | | | | | | 1) THERE ARE MISSING DIGITAL SIGNATURES ON THE ENERGY | | | GAUGE COMPLIANCE SUBMITTAL (PAGE 3), THE HEAT LOAD | | | CALCULATIONS, THE HEAT LOAD INDEX, THE STRUCTURAL | | | ANALYSIS FROM STEVE WALSH P.E, AND SHEETS M1.01, M1.02, | | | M1.05, M1.06, M4.01, M4.02, M4.03, M5.01, & M5.03. | | | | | | 2) SHEET A0.01 HAS NOT BEEN CORRECTED TO SHOW THE | | | CORRECT BUILDING NUMBER AND TYPE WHICH IS BUILDING III, | | | TYPE-1. | | | | | | 3) PLEASE SEE PAGES 2 & 3 OF THE AC STAND NOA | | | #15-0205.01 AND CIRCLE OR MARK THE SELECTED STAND FRAME | | | ASSEMBLY IN THE DESIGN SCHEDULE ON PAGE 2, AND THE | | | APPLICABLE AC AND AC STAND ATTACHMENT DETAILS ON PAGE | | | 3. | | | | | | 4) THE STRUCTURAL ANALYSIS FROM WALSH ENGINEERING IS | | | INCORRECTLY TITLED BUIDING 1. | | | | | | 5) SHEETS M4.02: PLEASE INDICATE THE SIZE OF THE LAST | | | SECTION OF EACH BRANCH DUCT ENTERING INTO BEDROOM #2 IN | | | UNITS B1 & B1.R. | | | | | | 6) FINAL APPROVAL OF NATURAL VENTILATION DESIGN FOR THE | | | GARAGES IS PENDING FINAL APPROVAL BY THE WPB FIRE DEPT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|