Plan Review Notes
Plan Review Notes For Permit 15120896
Permit Number 15120896
Review Stop B
Sequence Number 3
Notes
Date Text
2016-07-19 09:33:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120896
 ADD: 7140 OKEECHOBEE BLVD. BLDG. # 3/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 3RD REVIEW
 DATE: MON. JULY 19/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING# 3. BUILDING TYPE I,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) IN REVIEW BY BUILDING OFFICIAL. THE PERMIT
 APPLICATION VALUE OF $4,000,000.00 DOLLARS IS LOW. THE
 AUGUST 2015 ICC VALUATION TABLES LIST THE VALUE AT:
 BUILDING TYPE: III B 73,112 SQ. FT. X $123.25/ SQ. FT.=
 $9,011,054.00 DOLLARS.
 NOTE, THE MEP AND ROOFING PERMITS, ARE SUB-PERMITS AND
 IF NOT SUBMITTED AT THE TIME OF PERMIT ARE A $80.00
 SUB-PERMIT AND ARE INCLUDED IN THE VALUE OF THE
 BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED PERMITS.
 PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS FOR THE
 BUILDING, SUBMIT A LIST OF PERMITS AND BREAK-OUT THE
 VALUE FROM THE TOTAL COST TO DETERMINE THE FINAL
 VALUATION OF THE BUILDING PERMIT.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) COMPLIED. THRESHOLD BUILDING.
  
 2F) INFORMATIONAL. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE.
  
 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-5)COMPLIED.
  
 6) SEMI-COMPLIED. ENERGY CALCULATIONS WERE SUBMITTED
 DIGITALLY. PLEASE NOTE THAT THEY DO NOT HAVE AN
 ELECTRONIC SIGNATURE. IF THE DESIGNER DOES NOT SIGN
 THEM ELECTRONICALLY, PLEASE SUBMIT AN ORIGINAL SIGNED
 AND SEALED SET OF CALCULATIONS, THEY THEN WILL BE FILED
 WITH THE OTHER PAPER DOCUMENTS FOR THIS PERMIT.
  
 7) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
  
 8) COMPLIED.
  
 9A-9E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
  
 9B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 9E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 9F) COMPLIED. A/C STANDS.
  
 10) BUILDING PROVISO/ DEFERRED SUBMITTAL:
  
 10A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 10B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 10C) DEFERRED SUBMITTAL. THIS IS A VERY RESTICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11A-D) COMPLIED.
  
 11E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11F-I) COMPLIED.
  
 12-14) COMPLIED.
  
 15) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 16-18) COMPLIED.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) PLEASE NOTE NONE OF THE STRUCTURAL SHEETS HAVE
 ELECTRONIC SIGNATURES. 61G15-23.005 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 21) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  