Plan Review Notes
Plan Review Notes For Permit 15120896
Permit Number 15120896
Review Stop P
Sequence Number 2
Notes
Date Text
2016-04-26 08:21:342ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE STORM RISER DIAGRAM FOR HORIZONTAL
 PIPING SIZING AND CLARIFICATION OF EMERGENCY ROOF DRAIN
 TERMINATION. PER WPB AMEND.TO FBC SEC. 107.3.5.1.3(7)
 2. SHT. A4.01 IT APPEARS THAT YOU CHANGED THE DOOR
 SWING IN MASTER BATHROOM FOR UNIT A.1R BUT NOT A.1
 PLEASE CLARIFY. PER WPB AMEND.TO FBC SEC. 107.2.1
 3. SHT. A4.02 AND A4.03 PLEASE INDICATE ON BOTH UNIT
 DETAILS WITCH OPTION YOUR USING FOR FAIR HOUSING. PER
 WPB AMEND.TO FBC SEC. 107.2.1
 4. SHT. A4.02 THE CLEAR FLOOR SPACE FOR THE SHOWER MUST
 BE FLUSH WITH CONTROL WALL IT WAS CORRECTED ON
 SHT.A4.03 BUT NOT ON A4.02. PER WPB AMEND.TO FBC SEC.
 107.2.1
 5. SHT. P5.01 PLEASE LABEL CONDENSATE RISER, WATER
 HEATER PAN DRAIN RISER AND POTABLE WATER RISER
 SEPARATELY BECAUSE THEY ARE DIFFERENT SYSTEMS. PER WPB
 AMEND.TO FBC SEC. 107.2.1
 6. PLEASE INDICATE ON THE PLAN THE PIPING FOR DOMESTIC
 PUMP IS FOR FUTURE USE. PER WPB AMEND.TO FBC SEC.
 107.2.1
  