2016-04-18 16:39:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120896
 ADD: 7140 OKEECHOBEE BLVD. BLDG. # 3/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: MON. APRIL 18/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING# 3. BUILDING TYPE I,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) 2ND REQUEST. THE PERMIT APPLICATION VALUE OF
 $4,000,000.00 DOLLARS IS LOW. THE AUGUST 2015 ICC
 VALUATION TABLES LIST THE VALUE AT: BUILDING TYPE: III
 B 73,112 SQ. FT. X $123.25/ SQ. FT.= $9,011,054.00
 DOLLARS.
 NOTE, THE MEP AND ROOFING PERMITS, ARE SUB-PERMITS AND
 IF NOT SUBMITTED AT THE TIME OF PERMIT ARE A $80.00
 SUB-PERMIT AND ARE INCLUDED IN THE VALUE OF THE
 BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED PERMITS.
 PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS FOR THE
 BUILDING, SUBMIT A LIST OF PERMITS AND BREAK-OUT THE
 VALUE FROM THE TOTAL COST TO DETERMINE THE FINAL
 VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE NOTE THIS 4 STORY BUILDING IS CONSIDERED A
 THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 2C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4/ 633 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, A INTERVIEW MAYBE SCHEDULED. UNDER
 NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED FOR
 WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
  
 2F) INFORMATIONAL. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
  
 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3)COMPLIED.
  
 4) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 5) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE
  
 6) 2ND REQUEST, NO ENERGY CALCS. UNDER THE 2014 ENERGY
 CODE THIS 4 STORY/ R2 OCCUPANCY IS CONSIDERED A
 COMMERCIAL BUILDING.
 RESIDENTIAL BUILDING. FOR THE PURPOSE OF THIS CODE,
 INCLUDES GROUP R-3 BUILDINGS, AS WELL AS GROUP R-2 AND
 R-4 BUILDINGS THREE STORIES OR LESS IN HEIGHT ABOVE
 GRADE PLANE.
  
 2014 FBC-ENERGY CODE C401.2. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 7) SEMI-COMPLIED. STRUCTURAL PLANS WERE SUBMITTED. THE
 INDEX SHEET SHOWS FOR STRUCTURAL SHEETS S1-S5 ARE TO BE
 WITHIN THIS SET OF DOCUMENTS.
 NO STRUCTURAL INSPECTION PLAN, NO SHORING AND RE-SHORE
 PLANS.
 8A) SHEET S-5 V1 DOES INDICATE BOTH WALL ZONES 4 & 5
 THE NEGATIVE PRESSURES ARE LOW FOR A FLAT ROOFED
 BUILDING AT 45 FEET ELEVATION, EXPOSURE C. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA, WIND DESIGN PRESSURES.
  
 8B) SHEET S-5 V1. THIS SHEET THE ROOF PRESSURES ARE LOW
 FOR THE FLAT ROOF , EXPOSURE C @ 45 FEET ELEVATION.
 PLEASE NOTE A SECOND SET OF ROOF PRESSURES WILL ALSO BE
 REQUIRED FOR THE ROOF SLOPE OF 5:12.
  
 9A-9E) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 9B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
  
 9C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIXE.
  
 9E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 9F) COMPLIED. A/C STANDS.
  
 10) 2ND REQUEST. THIS IS A GENERAL COMMENT THAT WILL
 PERTAIN TO ALL FLOORS. PLEASE PROVIDE TEST REPORTS
 SHOWING COMPLIANCE WITH:
 10A) 2ND REQUEST. NOTE THIS NOTE APPLIES TO FLOORS 2-4
 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 10B) 2ND REQUEST. THIS NOTE APPLIES TO WALLS AS WELL AS
 FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON SHEET
 A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED STC
 RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B 2014
 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 10C) 2ND REQUEST. THIS IS A VERY RESTICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11)2ND REQUEST 1ST FLOOR/ SHEET A2.02.1 & A401, A402 &
 A403:
  
 11A) 2ND REQUEST, PLEASE SHOW THE WALL TAG D AS
 INDICATED IN YOUR RESPONSE. COMMON CORRIDOR & BOTTOM
 RIGHT C-1. WALL TYPES NOT DEPICTED. IN SHEET A4.03 UNIT
 C,1 THE COMMON CORRIDOR TO THE RIGHT OF THE ENTRY DOOR
 IS IDENTIFIED WITH WALL TAG WALL TYPE (F). JUST TO THE
 LEFT OF THE ENTRY DOOR SHEET A2.02.1.1 INDICATES A ROOF
 DRAIN WALL TYPE IS NOT IDENTIFIED WITH A WALL TAG.
 ADDITIONAL INFORMATION REQUIRED FOR RATED WALL.
 107.2.13. 2014 FBC-B 1018.1 & TABLE 1018.1. FOR THIS
 TYPE DETAIL THIS COMMENT WILL BE COMMON FOR ALL FLOORS.
  
 FOR THE 2 & 3 BEDROOM UNITS THERE IS A NOTE 11
 INDICATING THE RAIN LETTER BUT NO NOTATION AS TO WALL
 TYPE COMMON COMMENT TO ALL FLOORS.
  
 11B) COMPLIED. STRUCTURAL SHEETS LOADED THIS REVIEW
  
 11C) COMPLIED.
 11D) COMPLIED.
  
 11E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11F)THIS COMMENT COMMON TO ALL FLOORS. PLEASE NOTE
 WITHIN THIS SET OFF DOCUMENTS THERE ARE NO LIFE SAFETY
 SHEETS TO REVIEW. PLEASE IDENTIFY THESE ISSUES ON THE
 ARCHITECTURAL FLOOR PLANS SINCE THEY RELATE TO THE
 BUILDING CODE REQUIREMENTS.
  
 11F) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE
 SLEEPING ROOMS!!!2014 FBC-B 420.5 SMOKE DETECTION AND
 FIRE ALARM SYSTEMS. FIRE ALARM SYSTEMS AND SMOKE ALARMS
 SHALL BE PROVIDED IN GROUP I-1, R-1 AND R-2 OCCUPANCIES
 IN ACCORDANCE WITH SECTIONS 907.2.6, 907.2.8 AND
 907.2.9, RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE
 ALARMS SHALL BE IN ACCORDANCE WITH SECTION 907.2.11.
  
 11G) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE
 SLEEPING ROOMS. THIS COMMENT COMMON TO ALL FLOORS.
 PLEASE NOTE WITHIN THIS SET OFF DOCUMENTS THERE ARE NO
 LIFE SAFETY SHEETS TO REVIEW. 2014 FBC-B 908.7 CARBON
 MONOXIDE PROTECTION. EVERY SEPARATE FOR WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL
 BURNING HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED
 GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT
 EMITS CARBON MONOXIDE AS A BYPRODUCT OF COMBUSTION
 SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM
 INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES IN THE NEW AT SUCH OTHER LOCATIONS AS REQUIRED
 BY THIS CODE.
 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON
 MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 11H) COMPLIED.
 11I-11L) COMPLIED.
  
 12) 2ND REQUEST. SEMI-COMPLIED. PLEASE REVIEW SHEET
 A3.01 THE RIGHT SIDE STAIRWELL ON THE FRONT ELEVATION
 SHOWS THE NEW 35 SQ. FOOT OPENING BUT NOT THE LEFT SIDE
 OF THE BUILDING.
 SHEET A3.02 SHOWS A OPEN STAIRWELL ON THE 1ST FLOOR
 THROUGH THE 4TH FLOOR BUT THE STAIRWAY FROM THE 4TH
 FLOOR TO THE ROOF DOES NOT MEET THE REQUIREMENTS FOR
 OPENNESS.
 2014 FBC-B 1026.3 OPEN SIDE. EXTERIOR EXIT STAIRWAYS
 AND RAMPS SERVING AS AN ELEMENT OF A REQUIRED MEANS OF
 EGRESS SHALL BE OPEN ON AT LEAST ONE SIDE. AN OPEN SIDE
 SHALL HAVE A MINIMUM OF 35 SQUARE FEET (3.3 M2) OF
 AGGREGATE OPEN AREA ADJACENT TO EACH FLOOR LEVEL AND
 THE LEVEL OF EACH INTERMEDIATE LANDING. THE REQUIRED
 OPEN AREA SHALL BE LOCATED NOT LESS THAN 42 INCHES
 (1067 MM) ABOVE THE ADJACENT FLOOR OR LANDING LEVEL.
 CONSTRUCTION FROM THE 4TH FLOOR WILL BE THAT REQUIRED
 FLOOR ENCLOSED STAIRS. 1022.2 CONSTRUCTION. FOR THIS
 CONSTRUCTION WE ARE LOOKING FOR A 1 HOUR ENCLOSURE.
  
 13) COMPLIED
  
 14) COMPLIED. SHEET A8.03:
  
 15) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 16) SHEET A4.01: UNIT A.1
  
 16A) PLEASE SHOW THE CLEAR FLOOR SPACE FOR ALL KITCHEN
 APPLIANCES. EITHER FRONTAL OR SIDE APPROACH IN
 ACCORDANCE WITH ANSI A117.1-98. 305.
  
 16B) UNIT A1 THE PLANS SHOW IN THE FIXTURE SCHEDULE
 NOTE 14 TO BE AN OVEN/ RANGE W/ MICROWAVE HOOD ABOVE.
 THE PLANS ARE SILENT AS TO THE APPROACH AND REACH
 RANGES. ANSI A117.1-98, 308.3.2 OBSTRUCTED HIGH REACH
 RANGE FIGURE 308.3.2 (A) AND 309. OPERABLE PARTS 309.2
 CLEAR FLOOR SPACE, 309.1 HEIGHT AND 309.4 OPERATIONS.
  
 17-18) COMPLIED
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) PLEASE NOTE FOR ELECTRONIC PLAN REVIEW PEDDS
 DOCUMENTS ARE NO LONGER BEING APPROVED SINCE THE
 FLORIDA DEPARTMENT OF TRANSPORTATION NO LONGER HAS IT
 AVAILABLE. THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS SHOW COMPLIANCE WITH THE FLORIDA ADMINISTRATIVE
 CODE:
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR
 IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND
 SHALL ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT;
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 NOTE: SOILS REPORTS AS WELL AS ENERGY CALCULATIONS IF
 THEY ARE NOT SUBMITTED WITH AN ELECTRONIC SIGNATURE
 WILL REQUIRE PAPER DOCUMENTS WITH WET SEAL AND ORIGINAL
 SIGNATURE, NOT PHOTOCOPIES.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  