| 2016-04-18 16:39:35 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120896 |
| | ADD: 7140 OKEECHOBEE BLVD. BLDG. # 3/ BLDG. TYPE: I |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: MON. APRIL 18/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR BUILDING# 3. BUILDING TYPE I, |
| | NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES. |
| | |
| | 1) 2ND REQUEST. THE PERMIT APPLICATION VALUE OF |
| | $4,000,000.00 DOLLARS IS LOW. THE AUGUST 2015 ICC |
| | VALUATION TABLES LIST THE VALUE AT: BUILDING TYPE: III |
| | B 73,112 SQ. FT. X $123.25/ SQ. FT.= $9,011,054.00 |
| | DOLLARS. |
| | NOTE, THE MEP AND ROOFING PERMITS, ARE SUB-PERMITS AND |
| | IF NOT SUBMITTED AT THE TIME OF PERMIT ARE A $80.00 |
| | SUB-PERMIT AND ARE INCLUDED IN THE VALUE OF THE |
| | BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED PERMITS. |
| | PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS FOR THE |
| | BUILDING, SUBMIT A LIST OF PERMITS AND BREAK-OUT THE |
| | VALUE FROM THE TOTAL COST TO DETERMINE THE FINAL |
| | VALUATION OF THE BUILDING PERMIT. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PLEASE NOTE THIS 4 STORY BUILDING IS CONSIDERED A |
| | THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING |
| | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. |
| | |
| | 2C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4/ 633 FLORIDA STATUTE. |
| | |
| | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, A INTERVIEW MAYBE SCHEDULED. UNDER |
| | NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED FOR |
| | WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | |
| | 2F) INFORMATIONAL. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| | PRINT MAYBE IN BLACK & WHITE.. |
| | |
| | 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE |
| | CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6 |
| | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3)COMPLIED. |
| | |
| | 4) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 5) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY / FLOOD ZONE |
| | |
| | 6) 2ND REQUEST, NO ENERGY CALCS. UNDER THE 2014 ENERGY |
| | CODE THIS 4 STORY/ R2 OCCUPANCY IS CONSIDERED A |
| | COMMERCIAL BUILDING. |
| | RESIDENTIAL BUILDING. FOR THE PURPOSE OF THIS CODE, |
| | INCLUDES GROUP R-3 BUILDINGS, AS WELL AS GROUP R-2 AND |
| | R-4 BUILDINGS THREE STORIES OR LESS IN HEIGHT ABOVE |
| | GRADE PLANE. |
| | |
| | 2014 FBC-ENERGY CODE C401.2. COMMERCIAL BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 7) SEMI-COMPLIED. STRUCTURAL PLANS WERE SUBMITTED. THE |
| | INDEX SHEET SHOWS FOR STRUCTURAL SHEETS S1-S5 ARE TO BE |
| | WITHIN THIS SET OF DOCUMENTS. |
| | NO STRUCTURAL INSPECTION PLAN, NO SHORING AND RE-SHORE |
| | PLANS. |
| | 8A) SHEET S-5 V1 DOES INDICATE BOTH WALL ZONES 4 & 5 |
| | THE NEGATIVE PRESSURES ARE LOW FOR A FLAT ROOFED |
| | BUILDING AT 45 FEET ELEVATION, EXPOSURE C. 2014 FBC-B |
| | 1603.1.4 WIND DESIGN DATA, WIND DESIGN PRESSURES. |
| | |
| | 8B) SHEET S-5 V1. THIS SHEET THE ROOF PRESSURES ARE LOW |
| | FOR THE FLAT ROOF , EXPOSURE C @ 45 FEET ELEVATION. |
| | PLEASE NOTE A SECOND SET OF ROOF PRESSURES WILL ALSO BE |
| | REQUIRED FOR THE ROOF SLOPE OF 5:12. |
| | |
| | 9A-9E) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | |
| | 9B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | |
| | 9C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIXE. |
| | |
| | 9E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO |
| | RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA |
| | ARCHITECT OR ENGINEER. |
| | |
| | 9F) COMPLIED. A/C STANDS. |
| | |
| | 10) 2ND REQUEST. THIS IS A GENERAL COMMENT THAT WILL |
| | PERTAIN TO ALL FLOORS. PLEASE PROVIDE TEST REPORTS |
| | SHOWING COMPLIANCE WITH: |
| | 10A) 2ND REQUEST. NOTE THIS NOTE APPLIES TO FLOORS 2-4 |
| | ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 10B) 2ND REQUEST. THIS NOTE APPLIES TO WALLS AS WELL AS |
| | FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON SHEET |
| | A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED STC |
| | RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B 2014 |
| | 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 10C) 2ND REQUEST. THIS IS A VERY RESTICTIVE |
| | REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 11)2ND REQUEST 1ST FLOOR/ SHEET A2.02.1 & A401, A402 & |
| | A403: |
| | |
| | 11A) 2ND REQUEST, PLEASE SHOW THE WALL TAG D AS |
| | INDICATED IN YOUR RESPONSE. COMMON CORRIDOR & BOTTOM |
| | RIGHT C-1. WALL TYPES NOT DEPICTED. IN SHEET A4.03 UNIT |
| | C,1 THE COMMON CORRIDOR TO THE RIGHT OF THE ENTRY DOOR |
| | IS IDENTIFIED WITH WALL TAG WALL TYPE (F). JUST TO THE |
| | LEFT OF THE ENTRY DOOR SHEET A2.02.1.1 INDICATES A ROOF |
| | DRAIN WALL TYPE IS NOT IDENTIFIED WITH A WALL TAG. |
| | ADDITIONAL INFORMATION REQUIRED FOR RATED WALL. |
| | 107.2.13. 2014 FBC-B 1018.1 & TABLE 1018.1. FOR THIS |
| | TYPE DETAIL THIS COMMENT WILL BE COMMON FOR ALL FLOORS. |
| | |
| | FOR THE 2 & 3 BEDROOM UNITS THERE IS A NOTE 11 |
| | INDICATING THE RAIN LETTER BUT NO NOTATION AS TO WALL |
| | TYPE COMMON COMMENT TO ALL FLOORS. |
| | |
| | 11B) COMPLIED. STRUCTURAL SHEETS LOADED THIS REVIEW |
| | |
| | 11C) COMPLIED. |
| | 11D) COMPLIED. |
| | |
| | 11E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & |
| | E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5 |
| | AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR |
| | OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE |
| | WITH UL 325. IF THERE IS A POWER FAILURE OR A |
| | MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS |
| | HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11F)THIS COMMENT COMMON TO ALL FLOORS. PLEASE NOTE |
| | WITHIN THIS SET OFF DOCUMENTS THERE ARE NO LIFE SAFETY |
| | SHEETS TO REVIEW. PLEASE IDENTIFY THESE ISSUES ON THE |
| | ARCHITECTURAL FLOOR PLANS SINCE THEY RELATE TO THE |
| | BUILDING CODE REQUIREMENTS. |
| | |
| | 11F) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE |
| | SLEEPING ROOMS!!!2014 FBC-B 420.5 SMOKE DETECTION AND |
| | FIRE ALARM SYSTEMS. FIRE ALARM SYSTEMS AND SMOKE ALARMS |
| | SHALL BE PROVIDED IN GROUP I-1, R-1 AND R-2 OCCUPANCIES |
| | IN ACCORDANCE WITH SECTIONS 907.2.6, 907.2.8 AND |
| | 907.2.9, RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE |
| | ALARMS SHALL BE IN ACCORDANCE WITH SECTION 907.2.11. |
| | |
| | 11G) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE |
| | SLEEPING ROOMS. THIS COMMENT COMMON TO ALL FLOORS. |
| | PLEASE NOTE WITHIN THIS SET OFF DOCUMENTS THERE ARE NO |
| | LIFE SAFETY SHEETS TO REVIEW. 2014 FBC-B 908.7 CARBON |
| | MONOXIDE PROTECTION. EVERY SEPARATE FOR WHICH A PERMIT |
| | FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL |
| | BURNING HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED |
| | GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT |
| | EMITS CARBON MONOXIDE AS A BYPRODUCT OF COMBUSTION |
| | SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM |
| | INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING |
| | PURPOSES IN THE NEW AT SUCH OTHER LOCATIONS AS REQUIRED |
| | BY THIS CODE. |
| | 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON |
| | MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | 11H) COMPLIED. |
| | 11I-11L) COMPLIED. |
| | |
| | 12) 2ND REQUEST. SEMI-COMPLIED. PLEASE REVIEW SHEET |
| | A3.01 THE RIGHT SIDE STAIRWELL ON THE FRONT ELEVATION |
| | SHOWS THE NEW 35 SQ. FOOT OPENING BUT NOT THE LEFT SIDE |
| | OF THE BUILDING. |
| | SHEET A3.02 SHOWS A OPEN STAIRWELL ON THE 1ST FLOOR |
| | THROUGH THE 4TH FLOOR BUT THE STAIRWAY FROM THE 4TH |
| | FLOOR TO THE ROOF DOES NOT MEET THE REQUIREMENTS FOR |
| | OPENNESS. |
| | 2014 FBC-B 1026.3 OPEN SIDE. EXTERIOR EXIT STAIRWAYS |
| | AND RAMPS SERVING AS AN ELEMENT OF A REQUIRED MEANS OF |
| | EGRESS SHALL BE OPEN ON AT LEAST ONE SIDE. AN OPEN SIDE |
| | SHALL HAVE A MINIMUM OF 35 SQUARE FEET (3.3 M2) OF |
| | AGGREGATE OPEN AREA ADJACENT TO EACH FLOOR LEVEL AND |
| | THE LEVEL OF EACH INTERMEDIATE LANDING. THE REQUIRED |
| | OPEN AREA SHALL BE LOCATED NOT LESS THAN 42 INCHES |
| | (1067 MM) ABOVE THE ADJACENT FLOOR OR LANDING LEVEL. |
| | CONSTRUCTION FROM THE 4TH FLOOR WILL BE THAT REQUIRED |
| | FLOOR ENCLOSED STAIRS. 1022.2 CONSTRUCTION. FOR THIS |
| | CONSTRUCTION WE ARE LOOKING FOR A 1 HOUR ENCLOSURE. |
| | |
| | 13) COMPLIED |
| | |
| | 14) COMPLIED. SHEET A8.03: |
| | |
| | 15) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL |
| | WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT |
| | APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 . |
| | |
| | 16) SHEET A4.01: UNIT A.1 |
| | |
| | 16A) PLEASE SHOW THE CLEAR FLOOR SPACE FOR ALL KITCHEN |
| | APPLIANCES. EITHER FRONTAL OR SIDE APPROACH IN |
| | ACCORDANCE WITH ANSI A117.1-98. 305. |
| | |
| | 16B) UNIT A1 THE PLANS SHOW IN THE FIXTURE SCHEDULE |
| | NOTE 14 TO BE AN OVEN/ RANGE W/ MICROWAVE HOOD ABOVE. |
| | THE PLANS ARE SILENT AS TO THE APPROACH AND REACH |
| | RANGES. ANSI A117.1-98, 308.3.2 OBSTRUCTED HIGH REACH |
| | RANGE FIGURE 308.3.2 (A) AND 309. OPERABLE PARTS 309.2 |
| | CLEAR FLOOR SPACE, 309.1 HEIGHT AND 309.4 OPERATIONS. |
| | |
| | 17-18) COMPLIED |
| | |
| | 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 20) PLEASE NOTE FOR ELECTRONIC PLAN REVIEW PEDDS |
| | DOCUMENTS ARE NO LONGER BEING APPROVED SINCE THE |
| | FLORIDA DEPARTMENT OF TRANSPORTATION NO LONGER HAS IT |
| | AVAILABLE. THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL |
| | SHEETS SHOW COMPLIANCE WITH THE FLORIDA ADMINISTRATIVE |
| | CODE: |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL |
| | SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR |
| | IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND |
| | SHALL ASSURE THAT THE DIGITAL SIGNATURE IS: |
| | (A) UNIQUE TO THE PERSON USING IT; |
| | (B) CAPABLE OF VERIFICATION; |
| | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; |
| | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE |
| | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE |
| | DOCUMENT ARE CHANGED. |
| | NOTE: SOILS REPORTS AS WELL AS ENERGY CALCULATIONS IF |
| | THEY ARE NOT SUBMITTED WITH AN ELECTRONIC SIGNATURE |
| | WILL REQUIRE PAPER DOCUMENTS WITH WET SEAL AND ORIGINAL |
| | SIGNATURE, NOT PHOTOCOPIES. |
| | |
| | 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |