| 2016-02-09 05:24:09 | 1) SHT.A3.06E - THE HYDRAULIC ELEVATOR SHALL COMPLY |
| | WITH 2014 FBC SEC.3011 FOR ELECTROLYSIS PROTECTION. |
| | 2) INDICATE ON THE PLANS WHICH DESIGN OPTION OF THE |
| | FAIR HOUSING ACT (OPTION A OR B) IS BEING USED FOR THE |
| | DWELLING UNITS. |
| | 3) THE WATER VALVES FOR THE STACKED WASHER/DRYER UNITS |
| | SHALL BE ACCESSIBLE. THE VALVES SHALL NOT BE LOCATED |
| | BEHIND THE UNIT UNLESS ACCESS PANELS FOR THE VALVES ARE |
| | PROVIDED IN THE UNITS.2014 FPC SEC.606.3. |
| | 4) SHT. A4.01 - UNIT A.1 DETAIL & A.1R - A 30 X 48 INCH |
| | CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING OF THE |
| | DOOR PER THE FAIR HOUSING ACT GUIDELINES.THE DOOR |
| | CLEARLY SWINGS INTO THE CLEAR FLOOR SPACE FOR THE TUB. |
| | 5) THE WATER CLOSETS SHALL BE LOCATED 18 INCHES FROM AN |
| | ADJACENT WALL IN ACCORDANCE WITH THE FAIR HOUSING |
| | GUIDELINES. THE PLANS SHOW WATER CLOSETS AT 18 1/2 |
| | INCHES TO THE CENTERLINE FROM AN ADJACENT WALL. |
| | 6) THERE SHALL BE A 30 X 48 INCH CLEAR FLOOR SPACE |
| | PROVIDED AT THE KITCHEN SINK. THE CLEAR FLOOR SPACE |
| | SHALL BE CENTERED ON THE FIXTURE IN ACCORDANCE WITH THE |
| | FAIR HOUSING GUIDELINES. |
| | 7) SHT. A4.03 - DETAIL C.1 & C.1R - THE CLEAR FLOOR |
| | SPACE FOR THE SHOWERS SHALL BE FLUSH WITH THE CONTROL |
| | WALL PER THE GUIDELINES. THE PLANS SHAOW THE CLEAR |
| | FLOOR SPACE FLUSH WITH THE WALL WITH THE TOWEL BAR. |
| | THIS DOES NOT COMPLY WITH THE GUIDELINES. |
| | 8) SHT. 8.03 - BLOCKING DETAIL #8 - THE MAXIMUM |
| | DISTANCE TO THE BOTTOM OF THE REINFORCEMENT ABOVE THE |
| | TOP OF THE TUB SHALL BE 6 INCHES PER FIGURE #4 OF THE |
| | GUIDELINES. SEE THE BACK WALL DETAIL. PLACE A NOTE THAT |
| | THE 3'-2" MEASUREMENT IS MINIMUM TO THE TOP OF THE |
| | BACKING. |
| | 9) PER THE GUIDELINES, THE SEAT BLOCKING IN 36 INCH BY |
| | 36 INCH SHOWERS SHALL BE LOCATED ON THE WALL OPPOSITE |
| | THE CONTROLS AND MUST BE RUN THE FULL WIDTH OF THE |
| | SHOWER STALL , STARTING AT THE FLOOR TO A MINIMUM |
| | HEIGHT OF 24 INCHES WHEN THE SHOWER IS THE ONLY BATHING |
| | FIXTURE IN THE UNIT. |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL |
| | SMART PUMP SYSTEM. FBC SEC. 107.2.1. |
| | 11) THE HUB DRAIN AND THE FLOOR DRAIN IN THE TRASH ROOM |
| | SHALL BE EQUIPPED WITH TRAP PRIMERS PER 2014 FPC SEC. |
| | 1002.4. |
| | 12) SHT. P5.01 - THE CONDENSATE DRAIN RISERS AND THE |
| | WATER RISERS ARE IDENTIFIED WITH THE SAME |
| | IDENTIFICATION TAGS. PLEASE REVISE THE I.D. TAGS SO THE |
| | RISERS ARE NOT CONFUSED WITH EACH OTHER. 2014 FBC SEC. |
| | 107.2.1. |
| | 13) SUBMIT DETAILS FOR THE DOMESTIC WATER PUMP 7 |
| | PIPING.2014 FBC SEC. 107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |