| 2016-02-11 16:22:21 | PERMIT # 15120896 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED REVIEW COMMENTS: |
| | |
| | 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | 2) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND |
| | WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL |
| | BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO |
| | CONSTRUCTION WORK. SEPARATE PLANS AND PERMITS NEEDED |
| | FOR PRIVATE UNDERGROUND FIRE LINE AND FIRE HYDRANTS. |
| | |
| | 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | |
| | 4) PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO |
| | EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED |
| | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | 6) 9.4.3 FIRE FIGHTER?S EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | 7) HARD-WIRED MULTI-STATION SMOKE ALARMS SHALL BE |
| | INSTALLED ON ALL LEVELS OF THE DWELLING UNIT, INSIDE |
| | EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS. (NFPA |
| | 101: 30.3.4.5) |
| | |
| | |