Plan Review Notes
Plan Review Notes For Permit 15120896
Permit Number 15120896
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-18 06:30:38INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR IF
 PART OF DESIGN, FIRE/DOMESTIC PUMPS, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS,
 ETC. A NOTE WILL SUFFICE.
 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM
 COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A
 WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN
 FOR THIS PROJECT. A NOTE WILL SUFFICE.
 3. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 4. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY UTILITY FOR APPROVAL. NEC 110.24 FBC 107
 5. ADD A NOTE REGARDING THE REQUIREMENTS OF FBC RES 314
 SMOKE/CO DETECTORS, SEE VERBIAGE IN THE CODE AS TO
 PLACEMENTS AND REQUIREMENTS.
 6. PLEASE CLARIFY THE SELECTION OF A #1 CONDUCTOR FOR
 THE ELEVATOR MOTOR 175A/3P OVERCURRENT SELECTION. SEE
 NEC 310.15B16 AND 430.22
 7. PLEASE ADD A FIRE STOP DETAIL FOR THE FEEDER
 PENETRATIONS THROUGH THE BUILDING FLOORS. FBC 107.3
 8. PER NEC 230.2 SPECIAL PERMISSION REQUIRED BY AHJ FOR
 THE TWO SERVICE LATERALS SHOWN TO THE BUILDING, TO BE
 SUBMITTED IN WRITING.
 9. LABEL MAINS IN THE ELECTRICAL ROOM TO INDICATE MAIN
 1 OF 2 AND 2 OF 2, ALSO COMPLY WITH THE REQUIRED
 SIGNAGE TO ASSIST FIRST RESPONDERS. NEC 230.70B
 10. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  