| Notes |
| Date |
Text |
| 2016-01-14 07:45:55 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120894 | | | 01/14/16 | | | | | | 1) SHEET M-1: THE NEW 24X12 TRANSFER AIR GRILL AND THE | | | EXISTING 24X24 GRILL ARE EACH UNDERSIZED PER SECTION | | | 601.5 FBC-14 MECHANICAL, EXCEPTION #2: 50 SQ.INCHES PER | | | 100 CFM'S REQUIRED. PLEASE CORRECT. | | | 2) M-1: KEYED NOTE #7 SPECIFYING FRESH AIR INTAKE | | | LOUVER MUST BE CHANGED TO #8. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|