| Plan Review Notes For Permit 15120894 |
| Permit Number |
15120894 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-11 17:26:26 | FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | -NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 25? OF MECHANICAL EQUIPMENT. | | | | | | -FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. | | | | | | -NEC 110.16 & 110.24 ARC FLASH HAZARD WARNING LABEL AND | | | AVAILABLE FAULT CURRENT CALCULATIONS. | | | | | | -NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO | | | BUILDING STRUCTURE AND THE CEILING FRAMING MEMBER BY | | | MECHANICAL | | | MEANS SUCH AS BOLTS, SCREWS, OR RIVETS. ( ADD TO NOTES | | | ) |
|