| Date |
Text |
| 2016-01-11 07:02:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120894 |
| | ADD: 400 S. AUSTRALIAN AVE. SUITE # 720 |
| | CONT: BARR COMMERCIAL CONSTRUCTION |
| | TEL: 954-418-2297 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 08/2016 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET / GN LIST THE APPLICABLE CODES AS THE |
| | 2010 FAMILY OF THE FBC. PLEASE NOTE STATWIDE ON JUNE |
| | 30/ 2015 STATEWIDE THE 2014 5TH EDITION OF THE FLORIDA |
| | BUILDING CODE WAS ADOPTED. |
| | |
| | 2) COVERSHEET / GN LIST THE APPLICABLE CODES NOTE (B) |
| | AS THE BROWARD COUNTY AMENDMENTS TO THE FFPC. PLEASE |
| | NOTE THIS NOTE WILL ALSO NEED TO BE UPDATED TO: 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 3) THE PERMIT APPLICATION UNDER THE HEADING OF THE |
| | VALUE OF THE PROJECT IS EXTREMELY LOW FOR THE AMOUNT OF |
| | NEW WORK SHOWN ON THE PLANS. SHEET A1.1 SHOWS THE NEW |
| | WALLS BEING INSTALLED. |
| | |
| | SHEET A1.1 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF |
| | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 4) PLEASE NOTE WITHIN THIS SET OF PLANS THERE WERE NO |
| | MEP NOR FIRE SPRINKLER PLANS SHOWING THE EXISITNG |
| | SPRINKLER HEAD LAYOUT AND IF THE NEW WALL LAY OUT WOULD |
| | AFFECT THE THE SPRINKLERHEADS CAUSING HEADS TO BE |
| | MOVED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS:BUILDING |
| | (5) SCHEMATIC FIRE SPRINKLER LAYOUT |
| | 107.3.5.1.2 ELECTRICAL |
| | 107.3.5.1.3 PLUMBING |
| | 107.3.5.1.4 MECHANICAL |
| | |
| | 5) SHEET A1.1 PROPOSED FLOOR LAYOUT, NEW WALL LAYOUT |
| | SHOWS A NEW DOOR INTO ROOM 104 (OPEN AREA), THIS DOOR |
| | DOES NOT COMPLY WITH THE: |
| | 2014 FBC-ACCESSIBLITY CODE SECTION 404.2.4 & FIGURE |
| | 404.2.4(A) WITH THE REQUIRED 60 INCHES AWAY FFROM THE |
| | DOOR MEASURED AT 18 INCHES LATCH SIDE OF THE DOOR. |
| | |
| | 6) SHEET A1.1 & A1.1A THE FRONT ENTRY DOOR WILL NEED TO |
| | COMPLY WITH 2014 FBC-ACCESSIBLITY CODE SECTION 404.2.4 |
| | & FIGURE 404.2.4(A) WITH THE REQUIRED 60 INCHES AWAY |
| | FFROM THE DOOR MEASURED AT 18 INCHES LATCH SIDE OF THE |
| | DOOR. |
| | |
| | PLEASE REVIEW: 2014 ACC. CODE 202.4.1 DISPROPORTIONATE |
| | COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |