| Plan Review Notes For Permit 15120875 |
| Permit Number |
15120875 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-03-14 09:53:18 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120875 | | | 3/14/16 | | | | | | 1) SHEET M1: THE 95,000 BTU TRANE ROOFTOP AC MUST BE | | | RATED AT A MINIMUM 11.4 EER: THE SCHEDULE IS INDICATING | | | 10.3- SEE TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. | | | 2) M1: THE MINIMUM VENTILATION RATE FOR THE LAB | | | ACCORDING TO TABLE 403.3 IS BASED ON AN OCCUPANT | | | DENSITY OF 25 PEOPLE PER 1000 SF., HOWEVER THE RATE ON | | | THE PLAN IS INDICATING ONLY 10 PPL FOR 958 SF.- PLEASE | | | CORRECT. | | | 3) M1: REFER TO SECTION 501.3.1(2) AND PROVIDE | | | CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN FOR THE | | | EXHAUST OUTLET. | | | 4) SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL | | | FOR THE EXHAUST LOUVER REVIEWED AND APPROVED WITH | | | SIGNATURE BY THE DESIGN PROFESSIONAL OF RECORD. | | | 5) INDICATE THE TYPE AND GAGE OF EXHAUST DUCT MATERIAL, | | | AND PROVIDE DUCT HANGING AND CONNECTION DETAILS FOR | | | BOTH THE EXHAUST AND SUPPLY DUCTS. | | | 6) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE NEW | | | RTU TO THE EXISTING CURB- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|