| 2016-03-10 07:44:19 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120875 |
| | ADD: 2 HARVARD CIRCLE SUITE 500 |
| | CONT: FISHER CONTRACTING |
| | TEL: 561-691-4716 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 13RD REVIEW |
| | DATE: THURS. MARCH 10/2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A-1: |
| | 1A) DOOR AT RECEPTION DESK REVISION REQUIRED TO SHOW |
| | COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE 404.2.4 |
| | MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A). |
| | |
| | 1B) THE EAST DOOR OF THE LAB LABELED C, REVISION |
| | REQUIRED TO SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY |
| | CODE 404.2.4 |
| | MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A). |
| | |
| | 1C) DOORS TO ACCESSIBLE RESTROOMS DO NOT HAVE THE 18 |
| | INCHES MANEUVERING CLEARANCES 2014 FBC- ACCESS. CODE |
| | 404.2.4./ FIGURE 404.2.4.1(A). SEE SECTION: |
| | 603.2.3 DOOR SWING. 2. WHERE THE TOILET ROOM OR BATHING |
| | ROOM IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND |
| | THE ARC OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO |
| | SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED |
| | FOR ANY FIXTURE. |
| | |
| | 2) NO HAZARDOUS CHEMICALS TO BE STORED OR USED ON SITE |
| | WITHOUT THE USE OF A CONTROL AREA, WITH 1 HOUR FIRE |
| | SEPARATION AND SEPARATE MECHANICAL UNIT. PLEASE SEE |
| | ATTACHED LIST OF CHEMICALS TO BE STORED ARE |
| | NON-HAZARDOUS, ALL ARE LIQUID IN STATE. |
| | |
| | CHEMICALS ON SITE: ALL ARE NON-HAZARDOUS, ALL ARE IN |
| | THE LIQUID STATE. A100 ML (0,2205 LBS.) QUANTITY OF |
| | EACH WILL BE ON SITE TO PERFORM DAILY ACTIVITIES. MSDS |
| | FOR EACH CHEMICAL HAS BEEN INCLUDED FOR REVIEW. |
| | |
| | PHENCYCLIDINE METABOLITE ENZYME IMMUNOASSAY |
| | |
| | COCAINE METABOLITE ENZYME IMMUNOASSAY |
| | |
| | AMPHETAMINES ENZYME IMMUNOASSAY |
| | |
| | METHADONE METABOLITE CALIBRATORS |
| | |
| | PROPOXYPHENE ENZYME IMMUNOASSAY |
| | |
| | NITROGEN GENERATOR: DUE TO INDUSTRY CHANGES, PHR WILL |
| | NOT BE INSTALLING A NITROGEN GENERATOR. |
| | |
| | LC/MS TOXICOLOGY ANALYZER: DUE TO INDUSTRY CHANGES, PHR |
| | WILL NOT BE INSTALLING A LC/MS TOXICOLOGY ANALYZER. |
| | |
| | AU400 IS A SELF-CONTAINED CHEMISTRY ANALYZER. NO SITE |
| | PREPARATION IS REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |