| 2016-02-19 16:19:57 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15120875 |
| | 2/19/16 |
| | |
| | 1) AN EXHAUST SYSTEM AT A RATE 1.0 CFM PER SQUARE FOOT |
| | IS REQUIRED FOR THE LAB AREA AND THE RECIRCULATION OF |
| | AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3 AND |
| | FOOTNOTE G. IN ADDITION, TABLE 403.3 REQUIRES OUTDOOR |
| | AIR FOR OCCUPANTS OF THE LAB AT 10 CFM PER PERSON AND |
| | .18 CFM PER SQUARE FOOT OF THE SPACE. PLEASE REFER TO |
| | SECTION 403.3 WHERE IT STATES THAT "VENTILATION RATES |
| | FOR OCCUPANCIES NOT REPRESENTED IN TABLE 403.3 SHALL BE |
| | THOSE FOR A LISTED OCCUPANCY CLASSIFICATION THAT IS |
| | MOST SIMILAR IN TERMS OF OCCUPANT DENSITY, ACTIVITIES |
| | AND BUILDING CONSTRUCTION; OR SHALL BE DETERMINED BY AN |
| | APPROVED ENGINEERING ANALYSIS." THE VENTILATION RATES |
| | LISTED ABOVE ARE DERIVED FROM THE "SCIENCE |
| | LABORATORIES" LISTING IN TABLE 403.3. PLEASE REVISE THE |
| | PLAN ACCORDINGLY. |
| | 2) THE BUILLDING RESPONSE NARRATIVE INDICATES THE |
| | NITROGEN GENERATOR SHALL NOT BE INSTALLED. PLEASE NOTE |
| | THAT IF TO BE INSTALLED A LATER DATE, EITHER A REVISION |
| | TO THIS PERMIT OR SEPARATE PERMIT WILL BE REQUIRED AT |
| | WHICH TIME A COMPLETE REVIEW OF THE GENERATOR |
| | SPECIFICATIONS AND EXHAUST SYSTEM MUST BE CONDUCTED AND |
| | COMPLIANCES IN ACCORDANCE WITH HAZARDOUS EXHAUST |
| | SYSTEMS MAY BE ENFORCED. |
| | 3) PLEASE PROVIDE ON THE PLAN A NARRATIVE TO CLARIFY |
| | THE PROCESSES THAT WILL OCCUR IN THE LAB INCLUDING AN |
| | ITEMIZED LIST OF CHEMICALS AND THEIR QUANTITIES, AND |
| | HOW THE CHEMICALS WILL BE DISPENSED AND STORED- REFER |
| | TO SECTIONS 502.8 AND 510.1 FBC-14 MECHANCIAL. |
| | 4) THE ARCHITECT OF RECORD JAMES C PAINE JR. DID NOT |
| | PROVIDE VALID SIGNATURES AND SEALS ON ONE OF THE TWO |
| | NEW PLAN SETS SUBMITTED- SEE SECTION 61G1-16.003 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | 5) TWO RTU-1 RETURN DUCTS DO NOT HAVE SIZES- ONE FROM |
| | THE CORRIDOR AND ONE FROM SHIPPING/RECEIVING. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |