2015-12-31 06:33:141) SUBMIT 2 COPIES OF A COMPLETE GAS PIPING DIAGRAM FOR
 REVIEW. THERE WAS NO GAS PIPING DIAGRAM ASSOCIATWD WITH
 THE POOL PERMIT.
  
 2). SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 3.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5). SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 7) THE GAS INSTALLATION SHALL BE INSTALLED BY
 CERTIFIED GAS OR PLUMBING CONTR.
  
 ***NOTE*** AN ELECTRIC PERMIT MAY ALSO BE REQUIRED.
 GAS BY SEPARATE PERMIT.
  
  