| 2015-12-30 16:52:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. THERE IS NO INDICATION OF THE OCCUPANCY OR THE | | | OCCUPANCY LOAD THIS EXIT DOOR SERVES. | | | | | | 2. THERE IS NO INDICATION OF THE INTERIOR FLOOR PLAN | | | THAT THIS DOOR SERVES. | | | | | | 3. THERE IS NO INDICATION OF THE LOCKING/LATCHING | | | DEVICE ON THIS DOOR. | | | | | | 4. THERE IS NO INDICATION OF THE EXIT HARDWARE ATTACHED | | | TO THIS DOOR. | | | | | | 5. THERE IS NO INDICATION OF AN EXIT SIGN OR EMERGENCY | | | LIGHT ON THE INSIDE OF THIS DOOR. | | | | | | 6. THIS INSTALLATION SHALL COMPLY WITH THE 5TH EDITION | | | OF THE FLORIDA FIRE PREVENTION CODE INCLUDING, BUT NOT | | | LIMITED TO, NFPA 101, CHAPTER 7, MEANS OF EGRESS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|