| 2016-02-08 09:40:58 | JOB PERMIT NUMBER: 15120858 |
| | JOB ADDRESS: 3071 CONTINENTAL DR |
| | WEST PALM BEACH 33407 |
| | DATE: FEB 8 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. 1 PLEASE ADD TO NOTES NEC 700.12 (F) (4) - EMERGENCY |
| | LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL |
| | AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA, |
| | EM LIGHTS MAY BE ON OWN CIRCUIT. |
| | 2. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. |
| | THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, |
| | SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE |
| | SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. ( THIS IS A |
| | RECOMMENDATION FOR THE PURPOSES OF LIFE SAFETY NO |
| | EXTERIOR SECURITY LIGHTING SHOWN WOULD BE A GOOD IDEA |
| | TO ADD FOR THE OUTSIDE OF THE BUILDING. ESPECIALLY TO |
| | ILLUMINATE ADA RAMP. ) |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |