Plan Review Notes
Plan Review Notes For Permit 15120847
Permit Number 15120847
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-17 13:29:242ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1.SHT. P.1 GREASE INTERCEPTOR CALCULATIONS ARE FOR A
 STANDARD CONCRETE VAULT TANK BUT YOU REFERENCE A CODE
 SEC THAT APPLIES TO A HYDROMECHANICAL GREASE
 INTERCEPTOR PLEASE CLARIFY.
 2. PLEASE PROVIDE PERMIT NUMBER FOR GREASE INTERCEPTOR
 INSTALLED BY LANDLORD PER WPB AMEND TO FBC SEC 107.2.1
 3. SHT. P.2 ON RISER DIAGRAM YOU CALL OUT A 1250 GAL
 CONCRETE GREASE TRAP ON THE FLOOR PLAN YOU CALL OUT A
 SCHIER GB250 PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC
 107.2.1
 4. SHT P.2 FLOOR DRAIN IN COOK LINE IN FRONT OF STEAMER
 , FLOOR DRAIN IN APPETIZER AREA INFRONT OF CHIP WARMER
 , THESE FLOOR DRAINS ARE NOT VENTED SHALL COMPLY WITH
 FBC PL SEC 901.1.2
 5. PROVIDE WATER RISER DIAGRAM . PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 6. SHT FS-3 THE PIPING CONNECTING FLOOR DRAINS DOES NOT
 MATCH P.2 PLEASE CLARIFY PER WPB AMEND TO FBC SEC
 107.2.1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved