| Notes |
| Date |
Text |
| 2016-03-14 12:08:41 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120847 | | | 3/14/16 | | | | | | 1) THE RESPONSE NARRATIVE FROM THE ENGINEER TO THE | | | PREVIOUS MECHANICAL COMMENTS IS STATING THAT THE DUCT | | | SMOKE DETECTORS ARE UNDER THE LANDLORD'S PERMIT. PLEASE | | | NOTE THE UPLOADED PLANS AND DOCUMENTS SHOW COMPLETE AC | | | SYSTEMS AND MUCH BE REVIEWED AND APPROVED AS SUCH. | | | OTHERWISE, THE SYSTEMS' DETAILS AND SPECIFICATIONS WILL | | | HAVE TO BE REMOVED FROM THE SCOPE OF THE PROJECT, BUT | | | THEN HOW WOULD THIS TENANT BUILD-OUT PERMIT BE FINALED | | | OUT FOR CO? PLEASE NOTE THAT THE REVISION #16030102 | | | THAT HAS BEEN SUBMITTED UNDER THE SHELL PERMIT | | | #15090236 HAS BEEN DISAPPROVED BY THE STRUCTURAL PLANS | | | EXAMINER. PLEASE REVIEW THE COMMENTS. | | | 2) ENERGY CALCULATIONS HAVE BEEN SUBMITTED FOR THE | | | PROPOSED PROJECT, HOWEVER NO AC COOLING AND HEATING | | | CALCULATIONS HAVE BEEN SUBMITTED- PLEASE SEE SECTION | | | C403.2.1 FBC-14 ENERGY CONSERVATION AND SUBMIT THE | | | CALCS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|