| 2016-02-04 18:31:32 | 1ST ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 5TH EDITION 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | |
| | (A) SHEET E1.0 |
| | 1. THE FLORIDA FIRE PREVENTION CODE IN FORCE FOR THIS |
| | PROJECT IS THE 2012 EDITION. |
| | (BELOW COMMENTS 2 & 3 ARE ADDITIONAL NOTES TO THE BOXES |
| | SECTION) |
| | 2. REVISE THIS SECTION TO INCLUDE: |
| | 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 5. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| | PADDLE FANS HEAVIER THAN 70 LBS. |
| | (B) SHEET E2.0 |
| | 3. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | (C) SHEET E3.0 |
| | 4. THOUGH YOU INDICATE A SIGN OUTLET ABOVE EVERY DOOR, |
| | THE PANEL SCHEDULE CALLS THEM EXIT SIGNS; NOT THE |
| | INTENT. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH |
| | COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY |
| | ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT |
| | LEAST ONE 20 AMP DEDICATED OUTLET IN AN ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR OUTLINE LIGHTING. SERVICE HALLWAYS OR CORRIDORS |
| | SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |