2016-01-13 06:45:321ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHALL INCLUDE EMPLOYEES IN OCCUPANT LOAD PER FBC
 SEC1604.1
 2.SHT. P.1 GREASE INTERCEPTOR CALCULATIONS ARE FOR A
 STANDARD CONCRETE VAULT TANK BUT YOU REFERENCE A CODE
 SEC THAT APPLIES TO A HYDROMECHANICAL GREASE
 INTERCEPTOR PLEASE CLARIFY.
 3. PLEASE PROVIDE PERMIT NUMBER FOR GREASE INTERCEPTOR
 INSTALLED BY LANDLORD PER WPB AMEND TO FBC SEC 107.2.1
 4. SHT. P.2 ON RISER DIAGRAM YOU CALL OUT A 1250 GAL
 CONCRETE GREASE TRAP ON THE FLOOR PLAN YOU CALL OUT A
 SCHIER GB250 PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC
 107.2.1
 5. SHT P.2 FLOOR DRAIN IN COOK LINE AREA NEXT TO
 PREP/DISHWASHER , FLOOR DRAIN IN APPETIZER AREA ,FLOOR
 DRAIN AND HUB DRAINS IN CASHERS AREA, FLOOR DRAIN IN
 WALKWAY BETWEEN THE PREPP/DISHWASHER AND THE REST OF
 THE KIT AREA. THESE FOOR DRAIN ARE NOT VENTED SHALL
 COMPLY WITH FBC PL SEC 901.1.2
 6. PROVIDE WATER RISER DIAGRAM . PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 7. SHT FS-3 THE PIPING CONNECTING FLOOR DRAINS DOES NOT
 MATCH P.2 PLEASE CLARIFY PER WPB AMEND TO FBC SEC
 107.2.1