2016-01-04 14:47:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120847
 01/04/16
  
 1) SHEETS A0.1 & M1.1: THE SQUARE FOOT AREA
 CALCULATIONS SHOWN ON THESE PLAN SHEETS DO NOT MATCH-
 PLEASE REVIEW AND CORRECT.
 2) IN ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL,
 KITCHENS SHALL HAVE A REQUIRED EXHAUST RATE OF .7 PER
 SF. CLARIFY HOW THIS DEMAND IS BEING MET IN THE
 PREP/DISHWASH ROOM- NO EXHAUST IS SHOWN ON THE PLAN.
 3) INDICATE HOW THE DS DETECTORS WILL BE SUPERVISED,
 AND CLARIFY IF THE RTU'S WILL BE LINKED TO TOGETHER FOR
 SIMULTANEOUS SHUT-DOWN IF ANY SINGLE DETECTOR SHOULD
 ACTIVATE.
 4) THE CITY OF WPB REQUIRES SEPARATE PERMITS AND PLANS
 FOR THE KITCHEN HOOD AND EXHAUST SYSTEM, AND THE
 WALK-IN COOLER/FREEZER. PLEASE PLACE NOTES ON THE PLANS
 ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  