| 2016-02-02 18:46:29 | 1ST ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 5TH EDITION 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET E1.0 |
| | 1. THE FLORIDA FIRE PREVENTION CODE IN FORCE FOR THIS |
| | PROJECT IS THE 2014 EDITION. |
| | (BELOW COMMENTS 2 & 3 ARE ADDITIONAL NOTES TO THE BOXES |
| | SECTION) |
| | 2. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| | PADDLE FANS HEAVIER THAN 70 LBS. |
| | |
| | 4. MISSING ELECTRICAL SHEETS E2.0 & E3.0. PROVIDE THE |
| | MISSING SHEETS FOR ELECTRICAL REVIEW. PLEASE MAKE SURE |
| | THAT THE LIGHTING SHEET INCLUDES A FIXTURE SCHEDULE |
| | ALONG WITH THE REQUIRED ALLOWABLE LIGHTING DENSITY |
| | CHART INDICATING COMPLIANCE WITH THE FBC-EC405 |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |