Plan Review Notes
Plan Review Notes For Permit 15120847
Permit Number 15120847
Review Stop B
Sequence Number 1
Notes
Date Text
2016-01-11 11:15:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120847
 ADD: 2087 PALM BEACH LAKES BLVD
 CONT: TWT RESTAURANT DESIGN
 TEL: 813-886-8555
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 11/ 2016
 ACTION: DENIED
  
 1) SHEET A0.1:
  
 1A) WIND DESIGN CRITERIA, INDICATES THE ULTIMATE WIND
 LOAD OF 160 MPH. PLEASE SEE THE 2014 FBC-B FIGURE 1609A
 FOR CATEGORY II BUILDINGS, WEST PALM BEACH IS LOACATED
 IN A 170 VULT WIND ZONE. PLEASE CORRECT.
  
 1B) THE OCCUPANT LOAD TABLE UNDER THE 53 SQ. FT./5= 11
 NOT 10. WHEN THERE IS A FRACTION OF AN OCCUPANT YOU
 ROUND UP TO THE NEXT FULL OCCUPANT. 2014 FBC-B TABLE
 1004.1.2.
  
 2) SHEET A1.1;
  
 2A) SHEET A0.1 INDICATES INSIDE AND OUTSIDE SEATING
 THERE WILL BE 125 OCCUPANTS. SHEET A1.1 ONLY SHOWS ONE
 ACCESSBILE SEATING LOCATION. PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-ACC. CODE SECTION 226.1 WHICH REQUIRES AT
 LEAST 5% (OR 7 SEATS) OF THE SEATS SHALL COMPLY WITH
 902.
  
 2B) SHEET A0.1 ALSO WILL NEED TO SHOW WHERE THE 7 SEATS
 WILL BE DISPERSED THROUGHOUT AND SHOW COMPLIANCE WITH
 902.
  
 2C) PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH THE
 2014 FBC-ACC. CODE; 902.3 DINING SURFACES HEIGHT.
  
 2D) PLEASE PROVIDE FOR THE SEATING NEAREST THE
 RESTROOMS THE COMMON PATH OF TRAVEL FROM THE FURTHEST
 SEAT TO THE NEAREST EGRESS DOOR. SHOW COMPLIANCE WITH
 SECTION 1028.10.1.2 OF THE 2014 FBC-B SEATING AT TABLES
 AISLE ACCESS LEGTH SHALL NOT EXCEED 30 FT. WHERE A
 PERSON HAS A CHOICE OF 2 OR MORE PATHS OF EGRESS TRAVEL
 TO SEPARATE EXITS.
  
 2E) THE DOOR THAT LEADS INTO THE MENS RESTROOM, THERE
 IS A RECTANGLE THAT IS SHOWN 3/4'S THE WAY OFF THE
 WALL, WHAT IS REPRESENTED BY THIS FIGURE, THIS DOOR IS
 SUPPOSE TO HAVE 24 INCHES CLEAR SPACE, FROM THE LATCH
 APPROACH PULL SIDE OF THE DOOR. SEE 2014
 FBC-ACCESSIBILITY CODE FIGURE 404.2.4.1(H).
  
 3) SHEET M2.2:
  
 3A) PLEASE NOTE UNDER THE SHELL PERMIT ONLY THE ROOF
 TOP CURBS WERE BEING PERMITED. IT WILL BE THE
 RESPONSIBILITY OF THE TENANT BUILDOUT DESIGN TEAM TO
 SUPPLY THE WIND DESIGN FOR EQUIPMENT THAT WILL BE
 ANCHORED ABOVE THE ROOF LINE. THIS SHEET SHOWS A NEW
 PENETRATION THROUGH THE ROOF ASSEMBLY THE INTAKE FAN
 KEF-1. PLEASE PROVIDE STRUCTURAL SHEETS SHOWING THE NEW
 PENETRATION OF THE ROOF DECK, THE FRAMING AROUND THE
 NEW HOLE AND THE REQUIRED FASTENERS FOR THE NEW ROOF
 TOP CURB, AS WELL AS ROOF FRAMING FOR THE NEW ROOF TOP
 A/C STANDS. 2014 FBC-B , 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 3B) 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES. ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANSD.
  
 3C) PLEASE PROVIDE THE ATTACHMENT DETAILS FROM THE ROOF
 TOP CURB TO THE AIR HANDLERS AND FOM THE A/C STANDS TO
 THE ROOF TOP CONDENSING UNITS. 2014 FBC-B ,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 3D) PLEASE PROVIDE THE WIDTH OF THE ROOF TOP CONDENSING
 UNITS THAT WILL BE ATTACHED TO THE ROOF TOP STAND, TO
 SHOW COMPLIANCE WITH 2014 FBC-B TABLE 1522.3.
  
 3E) THIS SHEET DOES NOT INDICATE HOW ACCESS TO THE
 ROOFTOP EQUIPMENT WILL BE ACHIEVED? ? 1509.6.4
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676