| 2016-01-11 11:15:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120847 |
| | ADD: 2087 PALM BEACH LAKES BLVD |
| | CONT: TWT RESTAURANT DESIGN |
| | TEL: 813-886-8555 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 11/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.1: |
| | |
| | 1A) WIND DESIGN CRITERIA, INDICATES THE ULTIMATE WIND |
| | LOAD OF 160 MPH. PLEASE SEE THE 2014 FBC-B FIGURE 1609A |
| | FOR CATEGORY II BUILDINGS, WEST PALM BEACH IS LOACATED |
| | IN A 170 VULT WIND ZONE. PLEASE CORRECT. |
| | |
| | 1B) THE OCCUPANT LOAD TABLE UNDER THE 53 SQ. FT./5= 11 |
| | NOT 10. WHEN THERE IS A FRACTION OF AN OCCUPANT YOU |
| | ROUND UP TO THE NEXT FULL OCCUPANT. 2014 FBC-B TABLE |
| | 1004.1.2. |
| | |
| | 2) SHEET A1.1; |
| | |
| | 2A) SHEET A0.1 INDICATES INSIDE AND OUTSIDE SEATING |
| | THERE WILL BE 125 OCCUPANTS. SHEET A1.1 ONLY SHOWS ONE |
| | ACCESSBILE SEATING LOCATION. PLEASE SHOW COMPLIANCE |
| | WITH 2014 FBC-ACC. CODE SECTION 226.1 WHICH REQUIRES AT |
| | LEAST 5% (OR 7 SEATS) OF THE SEATS SHALL COMPLY WITH |
| | 902. |
| | |
| | 2B) SHEET A0.1 ALSO WILL NEED TO SHOW WHERE THE 7 SEATS |
| | WILL BE DISPERSED THROUGHOUT AND SHOW COMPLIANCE WITH |
| | 902. |
| | |
| | 2C) PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH THE |
| | 2014 FBC-ACC. CODE; 902.3 DINING SURFACES HEIGHT. |
| | |
| | 2D) PLEASE PROVIDE FOR THE SEATING NEAREST THE |
| | RESTROOMS THE COMMON PATH OF TRAVEL FROM THE FURTHEST |
| | SEAT TO THE NEAREST EGRESS DOOR. SHOW COMPLIANCE WITH |
| | SECTION 1028.10.1.2 OF THE 2014 FBC-B SEATING AT TABLES |
| | AISLE ACCESS LEGTH SHALL NOT EXCEED 30 FT. WHERE A |
| | PERSON HAS A CHOICE OF 2 OR MORE PATHS OF EGRESS TRAVEL |
| | TO SEPARATE EXITS. |
| | |
| | 2E) THE DOOR THAT LEADS INTO THE MENS RESTROOM, THERE |
| | IS A RECTANGLE THAT IS SHOWN 3/4'S THE WAY OFF THE |
| | WALL, WHAT IS REPRESENTED BY THIS FIGURE, THIS DOOR IS |
| | SUPPOSE TO HAVE 24 INCHES CLEAR SPACE, FROM THE LATCH |
| | APPROACH PULL SIDE OF THE DOOR. SEE 2014 |
| | FBC-ACCESSIBILITY CODE FIGURE 404.2.4.1(H). |
| | |
| | 3) SHEET M2.2: |
| | |
| | 3A) PLEASE NOTE UNDER THE SHELL PERMIT ONLY THE ROOF |
| | TOP CURBS WERE BEING PERMITED. IT WILL BE THE |
| | RESPONSIBILITY OF THE TENANT BUILDOUT DESIGN TEAM TO |
| | SUPPLY THE WIND DESIGN FOR EQUIPMENT THAT WILL BE |
| | ANCHORED ABOVE THE ROOF LINE. THIS SHEET SHOWS A NEW |
| | PENETRATION THROUGH THE ROOF ASSEMBLY THE INTAKE FAN |
| | KEF-1. PLEASE PROVIDE STRUCTURAL SHEETS SHOWING THE NEW |
| | PENETRATION OF THE ROOF DECK, THE FRAMING AROUND THE |
| | NEW HOLE AND THE REQUIRED FASTENERS FOR THE NEW ROOF |
| | TOP CURB, AS WELL AS ROOF FRAMING FOR THE NEW ROOF TOP |
| | A/C STANDS. 2014 FBC-B , 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 3B) 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES. ROOF TOP CURBS |
| | (G) PRE-ENGINEERED A/C STANSD. |
| | |
| | 3C) PLEASE PROVIDE THE ATTACHMENT DETAILS FROM THE ROOF |
| | TOP CURB TO THE AIR HANDLERS AND FOM THE A/C STANDS TO |
| | THE ROOF TOP CONDENSING UNITS. 2014 FBC-B , |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | 3D) PLEASE PROVIDE THE WIDTH OF THE ROOF TOP CONDENSING |
| | UNITS THAT WILL BE ATTACHED TO THE ROOF TOP STAND, TO |
| | SHOW COMPLIANCE WITH 2014 FBC-B TABLE 1522.3. |
| | |
| | 3E) THIS SHEET DOES NOT INDICATE HOW ACCESS TO THE |
| | ROOFTOP EQUIPMENT WILL BE ACHIEVED? ? 1509.6.4 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |