| Plan Review Notes For Permit 15120845 |
| Permit Number |
15120845 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-04 07:38:13 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120845 | | | 01/04/15 | | | | | | 1) SHEET #2: THE LOUVERED DOOR AT THE AHU CLOSET CANNOT | | | BE WOOD AS SPECIFIED IN THE SCHEDULE. IN ACCORDANCE | | | WITH C403.2.7.2 FBC-14 ENERGY CONSERVATION AND SECTION | | | 602 FBC-14 MECHANICAL THE DOOR SHALL BE MADE OF | | | NON-COMBUSTIBLE MATERIALS. | | | 2) SHEET #3: INDICATE A MEANS OF RETURN AIR FROM THE | | | BEDROOM AND THE GUEST ROOM IN ACCORDANCE WITH SECTION | | | 601.5 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|