| 2016-01-13 13:48:07 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. ACCORDING TO THE NOTES ON THE SUBMITTED PLANS, THE |
| | SERVICE IS TO BE RELOCATED. THE PERMIT APPLICATION |
| | SHALL BE REVISED TO INCLUDE THIS AS WELL. |
| | 2. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| | SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| | SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| | SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| | SITE SPECIFIC. |
| | 3. NEC 408.4 CIRCUIT DIRECTORY AND/OR IDENTIFICATION: |
| | THE CIRCUIT DIRECTORY AS SHOWN IS NOT CORRECT. THOUGH |
| | IT MAY MATCH THE LOADS INDICATED ON THE SUBMITTED SPEC |
| | SHEETS, THEY HAVE TO BE CORRECTED TO MATCH THE UNITS |
| | PROPOSED & INSTALLATION. ACCORDING TO THE SPEC SHEET |
| | AND THE PANEL SCHEDULES, YOUR GREATER LOADS ARE GOING |
| | TO THE CU RATHER THAN THE AH WHICH IS WHERE THE 9.6 KW |
| | HEATER IS TO BE PLACED. |
| | 4. THE OCP SHALL BE AS SPECIFIED ON THE UNIT NAME PLATE |
| | AND CORRECTED SPEC SHEET. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |