| 2016-04-01 14:44:38 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120750 |
| | ADD: 811A BELVEDERE RD. |
| | CONT: TBD |
| | TEL: 305-710-7178 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI., APRIL 01/2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) THIS TENANT SPACE BEING USED AS A MIXED USE |
| | OCCUPANCY, A1 OCCUPANCY(THEATER), A3 (PLACE OF WORSHIP) |
| | AND BUSINESS OCCUPANCY WILL BE LIMITED WITH PLACARD TO |
| | A OCCUPANT LOAD NOT TO EXCEED 49 OCCUPANTS PER : |
| | 2014 FBC-B 1004.3. POSTING OF OCCUPANT LOAD. |
| | EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL |
| | HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A |
| | CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS |
| | DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE |
| | OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE |
| | MAINTAINED BY THE OWNER OR AUTHORIZED AGENT. |
| | |
| | 2) AT TIME OF INSPECTION PLEASE PROVIDE COMPLIANCE WITH |
| | THE HUNG CURTAINS SEPARATING THE PRE-FUNCTION AND |
| | THEATER AREAS. SHOW COMPLIANCE WITH: |
| | 2014 FBC-B 806.1 IN OCCUPANCIES IN GROUPS A, E, I AND |
| | R-1 AND DORMITORIES IN GROUP R-2, CURTAINS, DRAPERIES, |
| | HANGINGS AND OTHER DECORATIVE MATERIALS SUSPENDED FROM |
| | WALLS OR CEILINGS SHALL MEET THE FLAME PROPAGATION |
| | PERFORMANCE CRITERIA OF NFPA 701 IN ACCORDANCE WITH |
| | SECTION 806.2 OR BE NONCOMBUSTIBLE. |
| | |
| | 2014 FBC-B 806.2 ACCEPTANCE CRITERIA AND REPORTS. WHERE |
| | REQUIRED BY SECTION 806.1, DECORATIVE MATERIALS SHALL |
| | BE TESTED BY AN AGENCY AND MEET THE FLAME PROPAGATION |
| | PERFORMANCE CRITERIA OF NFPA 701 OR SUCH MATERIALS |
| | SHALL BE NONCOMBUSTIBLE. REPORTS OF TEST RESULTS SHALL |
| | BE PREPARED IN ACCORDANCE WITH NFPA 701 AND FURNISHED |
| | TO THE BUILDING OFFICIAL UPON REQUEST. |
| | |