| Plan Review Notes For Permit 15120750 |
| Permit Number |
15120750 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-06 13:51:25 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS | | | | | | 1.PROVIDE PLUMBING RISER DIAGRAM WATER AND SANITARY PER | | | WPB AMEND TO FBC SEC107.3.5.1.3(13) | | | 2. YOUR PRIMARY OCCUPANCY IS ASSEMBLY A1 NOT BUSINESS | | | PER FBC 303.2 | | | 3. YOUR OCCUPANT LOAD SHALL BE CALCULATED BY USING THE | | | DIFFERENT AREAS PRESCRIBED IN FBC TABLE 1004 .2.1 | | | ASSEMBLY FIXED SEAT ,ASSEMBLY WITHOUT FIXED SEATS | | | STANDING ROOM 5 NET ,STAGES AND PLATFORMS 15 NET AND | | | BUSINESS | | | ALL THESE AREAS MUST BE CALCULATED SEPARATELY. | | | 4. A DRINKING FOUNTAIN COMPILING WITH FBC PL SEC410.2 | | | IS REQUIRED PER FBC PL TABLE 403.1 | | | 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
|