| 2016-02-08 15:44:49 | JOB PERMIT NUMBER: 15120750 |
| | JOB ADDRESS: 811 A BELVEDERE RD |
| | WEST PALM BEACH |
| | DATE: FEB 8 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1 NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. THIS APPLIES TO THE CU UNIT UP ON THE ROOF. |
| | 2 NEC 210.8 GFCI PROTECTION ??. (B) OTHER THAN DWELLING |
| | UNITS. AS FAR AS THE STAGE PERFORMANCE AREA RECEPTACLES |
| | WERE PORTABLE LIGHTING EQUIPMENT ARE TO BE USED. |
| | 3 NO LIGHTING CONTROLS IN OFFICE AREA PLEASE SEE FBC-E |
| | C405 AS A REFERENCE |
| | 4 FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 5 GENERAL NOTES STATE THAT A FIXTURE MOUNTING DETAIL |
| | SHALL BE FOUND IN ARCHITECTURAL ELEVATION? COULDN'T |
| | FIND ! |
| | 6 NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED |
| | 7 PROVIDE ARC FLASH AND AVAILABLE FAULT CURRENT FIELD |
| | LABELING NEC 110.16 / 110.24 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |
| | |