| 2015-12-29 06:04:25 | 1) THE PLANS INDICATE THAT THE EXISTING GAS WATER | | | HEATER IS BEING RELOCATED. SUBMIT A GAS AND WATER | | | PIPING RISER DIAGRAM FOR THE CHANGES TO THE GAS AND | | | WATER SYSTEMS. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 2) THE GATE VALVE SHALL BE LOCATED ON THE DISCHARGE | | | SIDE OF THE CHECK VALVE. 2014 FBC-PLUMBING SEC. 712.2. | | | 3) THE GATE AND CHECK VALVES SHALL BE | | | ACCESSIBLE.INDICATE ON THE PLANS HOW THIS WILL BE | | | ACCOMPLISHED.2014 FBC-PLUMBING SEC.712.2. | | | 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE LIFT | | | STATION. WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) THE CONNECTION OF THE DISCHARGE LINE TO THE BUILDING | | | DRAINAGE SYSTEM SHALL BE THROUGH A WYE FITTING INTO THE | | | TOP OF THE DRAINAGE PIPING IN ACCORDANCE WITH 2014 | | | FBC-PLUMBING SEC.712.3.5. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|