| Plan Review Notes For Permit 15120734 |
| Permit Number |
15120734 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-29 18:34:03 | MECHANICAL MASTER PERMIT #15030292 WAS NEVER ISSUED. IF | | | THESE ARE AS BUILT DRAWINGS, THE WORK WAS DONE WITHOUT | | | PERMITS. SEE COMMENTS FROM REVIEW FOR MASTER. | | | | | | THE PLANS THAT WERE SUBMITTED ARE NOT CLEAR. THERE IS | | | NO EQUIPMENT SCHEDULE. THE CFMS ARE NOT SHOWN. LOCATION | | | OF AIR HANDLE IS NOT CLEAR. LOCATION OF CONDENSING UNIT | | | IS NOT SHOWN. DISCONNECTS ARE NOT SHOWN. EQUIPMENT | | | ANCHORING IS NOT SHOWN. SUBMIT COMPLETE SCALED DRAWINGS | | | AND EQUIPMENT SIZING CALCULATIONS AS A RESUBMITTAL TO | | | THE MASTER PERMIT #15030292. FBC 107.3.5.3 |
|