2016-01-07 16:49:181ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PLEASE PROVIDE LOCATION OF ELECTRICAL EQUIPMENT IN
 RELATION TO EACH OTHER ON SITE PLAN. WPB FBC 107.3.1.2
 PLEASE GIVE ME A PANEL SCHEDULE SHOWING CIRCUIT
 IDETIFICATION WIRE, CONDUIT, AND PROTECTION SIZE NEC
 408.4
 FBC E C405.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE
 CONDUCTORS.
 FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE
 SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT AT DESIGN
 LOAD.
 FBC E C405.7.3.2 BRANCH CIRCUITS.
 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD.
 PROVIDE MAINTNANCE GFCI OUTLET FOR BOAT DOCKS NEC 555
 NEC 210.8C BOAT HOISTS. GFCI PROTECTION SHALL BE
 PROVIDED FOR
 OUTLETS NOT EXCEEDING 240 VOLTS THAT SUPPLY BOAT HOISTS
 INSTALLED
 IN DWELLING UNIT LOCATIONS.