2016-01-06 11:41:081) SUBMIT A NARRATIVE THAT CLEARLY DESRIBES THE CHANGES
 THAT WERE MADE TO THE PLUMBING SYSTEMS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) THE PLANS SHOW GAS APPLIANCES. THE GAS SHALL BE
 UNDER A SEPARATE PERMIT. THIS SHALL BE NOTED ON THE
 PLANS.TWO COPIES OF A GAS RISER ALONG WITH TWO COPIES
 OF MANUFACTURER'S SPECIFICATIONS FOR EACH GAS APPLIANCE
 SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION WHEN
 SUBMITTING FOR THE GAS PERMIT.
 3) SHT. A1 -SAN. RISER - BATH #4 - A VENT IS REQUIRED
 BETWEEN THE SHOWER AND TUB. 2014 FBCR SEC.P3101.2.
 4) SHT. A1 - SAN. RISER - VIP BATH - A VENT IS REQUIRED
 BETWEEN THE SHOWER AND THE WATER CLOSET. 2014 FBCR
 SEC.P3101.2.
 5) SHT. A1 - SAN.RISER - BATH #3 - A VENT IS REQUIRED
 BETWEEN THE SHOWER AND THE WATER CLOSET. 2014 FBCR
 SEC.P3101.2.
 6) SHT. A1 - SAN. RISER - THERE IS A FLAT, DRY VENT ON
 THE DRAIN AT THE FISH TANK ON THE 2ND FLOOR. THE VENT
 MUST BEE TAKEN OFF ABOVE THE CENTERLINE OF THE DRAIN TO
 WHICH IT CONNECTS. 2014 FBCR SEC. P3104.3.
 7) SHT. A5 SHOWS A POWER WASHER IN A/C STOR AREA #2,
 SHOW THE WATER CONNECTION TO THIS UNIT ON THE WATER
 RISER. IF IT IS SUPPLIED BY A HOSE FROM THE HOSE BIBB
 NOTE THIS ON THE PLAN.
 8) SHT. A6 - THE FLOR PLAN SHOWS A DRYER IN THE SECOND
 FLOOR LAUNDRY BUT NO WASHING MACHINE, BUT THE SANITARY
 AND WATER RISER SHOWS A WASHING MACHINE. CLARIFY.
 9) SHT. A6 - TWO LAVATORIES ARE SHOWN ON THE FLOOR PLAN
 IN THE MASTER BATH BUT ONLY ONE IS SHOWN ON THE
 SANITARY RISER.CLARIFY.
 10) ALL FLOOR DRAINS CONNECTED TO THE SANITARY SYSTEM
 SHALL BE EQUIPPED WITH TRAP PRIMERS. 2014 FBCR
 SEC.P3201.2.
  