| Plan Review Notes For Permit 15120711 |
| Permit Number |
15120711 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-12 08:24:56 | PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOM AND A | | | GFCI PROTECTED WALL RECEPTACLE OUTLET AT THE LAVATORY | | | PER 2014 FBCR E3703.4 & E3901.6. | | | INSTALL SMOKE ALARMS AS REQUIRED BY FBCR 314.3.1 |
|