2016-01-12 08:24:56PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOM AND A
 GFCI PROTECTED WALL RECEPTACLE OUTLET AT THE LAVATORY
 PER 2014 FBCR E3703.4 & E3901.6.
 INSTALL SMOKE ALARMS AS REQUIRED BY FBCR 314.3.1