| Plan Review Notes For Permit 15120707 |
| Permit Number |
15120707 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-14 10:09:20 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PROVISO : FACP B IN MECHANICAL ROOM DOESN'T HAVE A | | | SMOKE DETECTOR PLEASE INSTALL PRIOIR TO INSPECTION. | | | NFPA 72 2010 EDTION 10.15* PROTECTION OF FIRE ALARM | | | SYSTEM. IN AREAS THAT ARE NOT | | | CONTINUOUSLY OCCUPIED, AUTOMATIC SMOKE DETECTION SHALL | | | BE | | | PROVIDED AT THE LOCATION OF EACH FIRE ALARM CONTROL | | | UNIT(S), | | | NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS, AND | | | SUPERVISING | | | STATION TRANSMITTING EQUIPMENT TO PROVIDE NOTIFICATION | | | OF | | | FIRE AT THAT LOCATION. |
|