| Plan Review Notes For Permit 15120650 |
| Permit Number |
15120650 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-21 16:33:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1. SHEET FA - 03 - THERE IS AN INCORRECT REFERNCE TO | | | THE FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | | | | 2. ALL AUDIBLE LEVELS SHALL COMPLY WITH NFPA 101 | | | CHAPTER 31, EXISTING APARTMENT OCCUPANCIES, CHAPTER 9 | | | BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT; 9.6 | | | FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS, AND | | | NFPA 72. |
|