| Plan Review Notes For Permit 15120647 |
| Permit Number |
15120647 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-19 14:09:59 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120647 | | | 2/19/16 | | | | | | 1) SHEET M02.01: PLEASE REFER TO SECTION 606.2.2 FBC-14 | | | MECHANICAL- DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | | RETURN AIR SYSTEMS. | | | 2) M01.01: HP-4 AT 72MBH APPEARS TO BE OVERSIZED WHEN | | | COMPARE TO THE SUBMITTED AC CALCULATIONS INDICATING A | | | LOAD OF 37,5MBH- SEE SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|