Plan Review Notes
Plan Review Notes For Permit 15120647
Permit Number 15120647
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-30 14:40:101) SUBMIT MANUF. SPECIFICATIONS FOR THE DRAIN PUMP. WPB
 AMEND. TO FBC. SEC.107.2.1.
 2) THE PLUMBING RISER SHOWS A 3" W FROM DP 1 BUT THE
 DRAIN PUMP SCHEDULE ON SHT.P01.01 SHOWS THE DISCHARGE
 LINE AS 2". CLARIFY.
 3) THE PLUMBING RISER SHOWS THE 3"W FROM DP 1 ALSO
 CONNECTING TO THE VENT.IT APPEARS THAT THE WASTE WOULD
 ALSO BE PUMPED INTO THE VENT.CLARIFY.
 4) SHT.P01.01 - DETAIL #3 SHOWS A VALVE IN THE P & T
 LINE. 2014 FBC-PLUMBING SEC. 504.6 (12).
 5) MEANS SHALL BE PROVIDED TO CONTROL THERMAL EXPANSION
 IN ACCORDANCE WITH 2014 FBC-PLUMBING SEC.607.3
 6) A VALVE IS REQUIRED IN THE WATER SUPPLY LINE TO THE
 WATER HEATER. FBCP SEC.503.1.
  
 PLUMBING PLAN REVIEW